Whirlpool WFCT Installation Instructions Manual Download Page 8

8

Plan Vent System

The high efficiency of this furnace is accomplished by the 
removal of both sensible and latent heat from the flue gases. The 
removal of latent heat results in the condensation of moisture in 
the flue gases. This condensation occurs in the secondary heat 
exchanger and in the vent system. Therefore, this furnace 
requires special venting considerations, and the instructions 
must be followed to ensure proper operation. All venting must be 
in accordance with the codes having jurisdiction in the area and 
these instructions.

IMPORTANT:

The venting system must be supported with mounting straps 
to keep any weight load from being applied to the vent 
blower. Horizontal vent pipe must be supported every 5 ft 
(1.5 m) and vertical pipe should be supported every 10 ft 
(3 m) to avoid sagging and provide rigid support.

This furnace must not be connected to any Type B, BW, or 
L vent or vent connector and must not be connected to any 
portion of a factory-built or masonry chimney.

This furnace is not to be common vented with any other 
appliance. The vent pipe must not be connected to a 
chimney flue serving a separate appliance designed to burn 
solid fuel.

Materials

All pipe, fittings, primer, and solvent cement must conform 
with American National Standard Institute and the American 
Society for Testing and Materials (ANSI/ASTM) standards. 
The solvent shall be free flowing and contain no lumps, 
undissolved particles, or any foreign matter that adversely 
affects the joint strength or chemical resistance of the 
cement. The cement shall show no gelatinization, 
stratification, or separation that cannot be removed by 
stirring. See “Piping and Fitting Specifications” for approved 
piping and fitting materials.

Piping and Fitting Specifications

The primers and solvents used must also meet ASTM 
specifications. PVC primer is specified in ASTM F656. Use 
PVC solvent as specified in ASTM D2564 and ABS solvent 
cement as specified ASTM D2235. Low temperature solvent 
cement is recommended. Metal or plastic strapping may be 
used for vent pipe hangers.

When making ABS joints, pieces can be prepared with a 
cleaner. When joining ABS to PVC materials, use PVC solvent 
cement as specified in ASTM D3138.

Preferred fittings are DWV style or long sweep. Seal all joints 
gas tight with appropriate cement. In areas where vent and air 
intake pipes are exposed to abnormal stress or are subject to 
damage, schedule 80 pipe should be used.

Use high temperature RTV silicone sealant to attach the air 
intake pipe into the connector on the burner box so the air 
intake pipe can be removed if service is required.

NOTE: Do not use cement.

Vent Pipe Size and Length

The vent pipe and air intake pipe (in direct vent installations) should be sized in accordance with the information found in the Vent Table 
charts. One 90° elbow is equivalent to 5 ft (1.5 m) of pipe. Two 45° elbows are equivalent to one 90° elbow. The minimum length 
certified for use with this furnace is 5 ft (1.5 m) and one elbow, not including the vent and air intake terminals.      

Piping and Fitting Material

ASTM Specification

Schedule 40 PVC (Pipe)

D1785

Schedule 40 PVC (Cellular Core Pipe)

F891

Schedule 40 PVC (Fittings)

D2466

SDR-26 (Pipe)

D2241

Schedule 40 ABS (Pipe)

D1527

Schedule 40 ABS (Fittings)

D2468

Schedule 40 & 80 CPVC (Pipe)

F441

ABS-DWV Drain Waste & Vent 
(Pipe & Fittings)

D2661

PVC-DWV Drain Waste & Vent
(Pipe & Fittings)

D2665

Vent Table—40,000 to 80,000 Btu/h Models

Vent Pipe Length—ft (m) Minimum Pipe Diameter—in. (cm)

5 (1.5)

1

¹⁄₂ 

(3.8)

1

¹⁄₂ 

(3.8)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

10 (3)

1

¹⁄₂ 

(3.8)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

20 (6.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2

¹⁄₂

 (6.4)

30 (9.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2

¹⁄₂

 (6.4) 2

¹⁄₂

 (6.4) 2

¹⁄₂

 (6.4)

40 (12.2)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2 (5.1)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4) 2

¹⁄₂

 (6.4) 2

¹⁄₂

 (6.4) 2

¹⁄₂

 (6.4)

50 (15.2)

2 (5.1)

2 (5.1)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4) 2

¹⁄₂

 (6.4) 2

¹⁄₂

 (6.4) 3 (7.6)

60 (18.3)

2 (5.1)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4) 3 (7.6)

3 (7.6)

3 (7.6)

70 (21.3)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

3 (7.6)

3 (7.6)

3 (7.6)

3 (7.6)

NR

80 (24.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

3 (7.6)

3 (7.6)

3 (7.6)

3 (7.6)

3 (7.6)

NR

NR

90 (27.4)

2

¹⁄₂

 (6.4)

2

¹⁄₂

 (6.4)

3 (7.6)

3 (7.6)

3 (7.6)

3 (7.6)

3 (7.6)

NR

NR

NR

Number of 90º Elbows

0

1

2

3

4

5

6

7

8

9

 NR = Not Recommended

Summary of Contents for WFCT

Page 1: ... On 25 Cooling 25 CONTROLS 26 TROUBLESHOOTING 27 ASSISTANCE OR SERVICE 30 Accessories 30 47861B008 Whirlpool Home Cooling and Heating 14610 Breakers Drive Jacksonville FL 32258 Whirlpool and Whirlpool Gold Models WFCT WGFDT You can be killed or seriously injured if you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential ...

Page 2: ...ucts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace A gas fired furnace for installation in a residential garage must be installed as specified in the Location Requirements section of these instructions The furnace is not to be ...

Page 3: ...ed here Tools needed Parts needed Check local codes and with gas supplier Check existing gas supply electrical supply and venting and read Ductwork Requirements Electrical Requirements Gas Supply Requirements Venting Requirements and Installation Configurations before purchasing parts Parts supplied Inlet air restrictor plate Flue pipe screen Condensate disposal kit WARNING Gas leaks cannot always...

Page 4: ...not less than 18 45 7 cm above the floor The furnace is to be located or protected to avoid physical damage by vehicles Furnaces may be installed as suspended units in the horizontal position These furnaces are not designed for direct attachment of suspension rods to the furnace casing See installation Configurations If the furnace is to be installed in an attic or other insulated space it must be...

Page 5: ...or in the absence of local codes with the National Electrical Code ANSI NFPA No 70 latest edition In all instances other than wiring for the thermostat the wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire 63 F rise The line voltage supply should be routed through a readily accessible disconnect located within sight of the furnace A junctio...

Page 6: ...h temperature RTV sealant to attach the PVC to the inlet collar Flue Pipe Screen A flue pipe screen designed to keep objects out of the flue pipe is included in the plastic bag In all installations this screen should be installed at the termination of the flue pipe Flue Pipe Screen WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to t...

Page 7: ...s are met All provisions for indoor combustion air must meet the requirements for combustion air indicated in the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and or any applicable local codes If indoor combustion air is used the air supply to the furnace should not be exposed to the following substances Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming p...

Page 8: ...Metal or plastic strapping may be used for vent pipe hangers When making ABS joints pieces can be prepared with a cleaner When joining ABS to PVC materials use PVC solvent cement as specified in ASTM D3138 Preferred fittings are DWV style or long sweep Seal all joints gas tight with appropriate cement In areas where vent and air intake pipes are exposed to abnormal stress or are subject to damage ...

Page 9: ... terminal location shall comply with the National Fuel Gas Code ANSI Z223 1 or local requirements For informational purposes the side wall terminal vent clearances are shown in the Sidewall Vent Terminal Clearances tables Vent Table 90 000 to 100 000 Btu h Models Vent Pipe Length ft m Minimum Pipe Diameter in cm 5 1 5 NR 2 5 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 1 2 6 4 2 6 4 2 6 4 10 3 2 5 1 2 5 1 2 5 1 ...

Page 10: ...terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter regulator assembly I Clearance to service regulator vent outlet J Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 6 15 2 cm for appliances less than or equal to 10 000 Btu h 9 2...

Page 11: ...e terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter regulator assembly I Clearance to service regulator vent outlet J Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 48 121 9 cm below or to side of opening 12 30 5 cm above open...

Page 12: ...f the house within the parameters as shown NOTE The 18 45 7 cm dimension shown below is the minimum recommended height for extremely cold areas In these areas moisture in the flue gases may condense and freeze on the air intake if this height is reduced In milder climates this may be reduced to a minimum of 6 15 2 cm Height may be increased as needed provided total length of pipe to furnace is not...

Page 13: ...e flue pipe see Flue Pipe Screen in Venting Requirements should be installed at the termination of the flue pipe Nondirect Vent Upflow Horizontal Venting Nondirect Vent Upflow Vertical Venting A Run pitch 6 4 mm per foot minimum B Flue pipe screen inside flue pipe C 6 15 2 cm D 12 30 5 cm minimum clearance Adjust height to expected snow level based on local conditions E Air intake pipe F Condensat...

Page 14: ...side of the house within the parameters as shown NOTE The 18 45 7 cm dimension shown below is the minimum recommended height for extremely cold areas In these areas moisture in the flue gases may condense and freeze on the air intake if this height is reduced In milder climates this may be reduced to a minimum of 6 15 2 cm Height may be increased as needed provided total length of pipe to furnace ...

Page 15: ...ep objects out of the flue pipe see Flue Pipe Screen in Venting Requirements should be installed at the termination of the flue pipe Nondirect Vent Horizontal Horizontal Venting Horizontal Right to Left Nondirect Vent Horizontal Horizontal Venting Horizontal Left to Right A 6 15 2 cm minimum to roof Adjust height to expected snow level based on local conditions B 6 16 5 cm minimum to 24 61 cm maxi...

Page 16: ...n at the outside end of the flue pipe 7 Make sure all vent connections do not leak 8 Check that the exhaust vent pipe terminates outside the building 9 After the condensate disposal system has been installed prime the trap system by slowly pouring 8 oz 250 mL of water down the vent pipe The vent pipe on horizontal runs must slope upward away from the furnace at a minimum pitch of 6 4 mm per foot o...

Page 17: ...of the drain 3 Connect 1 9 cm PVC pipe make a connection from the adapter just installed to extend just outside the furnace Install a 1 9 cm PVC tee as shown 4 From the PVC tee connect the drain to the disposal area NOTE The top of the PVC tee must be left open for proper condensate drainage The open end of the PVC tee must be oriented so that the condensate does not run out of this opening Conden...

Page 18: ...pplied in kit into flue pan 4 Connect a length of PVC pipe 36 91 4 cm minimum to the external trap assembly supplied in kit 5 Install a 1 9 cm PVC tee as shown 6 From the 1 9 cm PVC tee connect the drain to the disposal area NOTE The top of the PVC tee must be left open for proper condensate drainage The open end of the PVC tee must be oriented so that the condensate does not run out of this openi...

Page 19: ...um of 9 22 9 cm above a surface such as a floor Install furnace at a slight pitch forward with shims or adjusting screws 1 Relocate 1 3 cm NPT plug from the flue pan to the internal trap assembly 2 Connect the 1 3 cm NPT plug supplied in kit to the opposite side of the internal trap assembly from the NPT plug installed in Step 1 3 Insert external trap assembly supplied in kit into the flue pan A 6...

Page 20: ...o the 0 10 W C pressure switch Other end of hose must be connected to external drain trap Route hose through gas line access hole in cabinet Then connect to barbed fitting on drain trap assembly IMPORTANT Be sure that the pressure switch hoses do not form a trap to hold condensation that could result from the flue gas Hose may be cut shorter to avoid forming a trap if required Horizontal Left to R...

Page 21: ...ewed for possible openings using light assistance or so that a probe can be inserted for sampling the airstream The cover for the opening must be leakproof FilterSpecifications Upflow Models A filter rack and cleanable 16 x 25 x 40 6 cm x 63 5 cm x 1 3 cm filter are supplied with this furnace Models designed for more than 1 600 CFM 487 7 m3 min nominal air delivery include two of each Some model f...

Page 22: ...RTANT This furnace requires conversion for use with propane To order the correct conversion kit see Accessories 1 Install the field gas supply as shown 2 Provide a sediment trap on the outside of the furnace 3 Install a manual gas shutoff valve in the gas line outside the furnace 5 ft 1 5 m above the floor or in accordance with any local codes 4 Install a test gauge connection with a 3 2 mm NPT pl...

Page 23: ...al gas and 10 25 4 cm W C for propane gas For natural gas check the furnace rate by observing the gas meter making sure all other gas appliances are turned off The test hand on the meter should be timed for at least one revolution At altitudes from 2 000 to 7 500 ft 609 6 m to 2 286 m the furnace input rate must not exceed that on the rating plate NOTE The actual heating value of your gas can be o...

Page 24: ...equired For the correct orifice size see Table F 4 in Appendix F of the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition CompleteInstallation IMPORTANT Do not use this furnace if any part has been under water Immediately call a qualified person to inspect the furnace and to replace any part of the control system and gas control which has been under water 1 Be sure you have all of your too...

Page 25: ...energizes the main valve causing the burners to shut off The induced draft blower shuts off after a 15 second post purge delay The circulating air blower will continue to operate until the user selectable heat blower off delay expires The control returns to standby mode once the heat blower off delay expires FanOn During a fan on call the thermostat energizes the R G circuit of the control board i...

Page 26: ...ns under abnormal reverse airflow conditions that could occur in a counterflow or horizontal installation if the circulating air blower fails It is an automatic reset control Safety Interlock Switch When the blower door is removed the safety interlock switch breaks the power supply to the burner controls and blower motor Ignition Control Board The ignition control board operates the gas valve circ...

Page 27: ...blem occurs a failure code is indicated by the LED on the ignition control board The control continuously monitors its own operation and the operation of the system If a failure occurs the LED will indicate the failure code IMPORTANT Do not remove the blower compartment door or turn off the power to the furnace since either action will clear the control s memory of the fault 1 Start the system by ...

Page 28: ...UM L1 XFMR CONT EAC COOL HEAT Hot Surface Igniter Interlock Switch Line Voltage Factory Line Voltage Field Low Voltage Factory Low Voltage Field Circulation Blower Not on all models Induced Draft Blower Pressure Switch Aux Limit Switch Check codes for proper wiring and circuit protection before installation NOTES 1 Press and release fault code history button to display fault codes To erase codes p...

Page 29: ... Gas Control Valve Flame Sensor Pin 3 Pin 2 Pin 6 Pin 5 Pin 11 Pin 1 Pin 7 Pin 10 Pin 4 Pin 8 Pin 9 Pin 12 If Used Rollout Switch Rollout Switch Hot Surface Igniter Neutrals Humidifier Induced Draft Blower Air Cleaner Heat Cool Blower Motor Transformer 24 VAC 120 VAC Interlock Switch Neutrals Neutrals Neutrals Neutrals Neutrals 120 1 60 ...

Page 30: ...610 Breakers Drive Jacksonville FL 32258 Please include a daytime phone number in your correspondence Accessories To order accessories ask for the appropriate part number listed below or contact your Whirlpool Home Cooling and Heating dealer ALPKT572 3 Natural Gas to Propane Conversion Kit AFILT524 1 Side Return Filter Kit AFILT529 1 Bottom Return Filter Kit ...

Page 31: ...31 Notes ...

Page 32: ...reserved Honeywell is a trademark of Honeywell International Inc Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Coconut Grove Florida 3 08 Printed in U S A ...

Reviews: