4-33
Maximum output
Frequency
Set frequency
Acc-time
00-14
Dec-time
00-15
Actual acc-time
Actual dec-time
Hz
T
0
The minimum
starting
frequency
00-18
Jog Frequency
Range
【
0.00~650.00
】
Hz
00-19
Jog Acceleration Time
Range
【
0.1~3600.0
】
Sec
00-20
Jog Deceleration Time
Range
【
0.1~3600.0
】
Sec
The JOG function is operational by using the multi-function input terminals S1 to S6 and setting the relevant
parameters 03-00~03-05 to
【
6
】
JOG FWD or
【
7
】
JOG REV. Refer to parameter group 3.
Notes:
- To activate the JOG FWD function set any of the multi-function input terminals S1 to S6 to 6.
- To activate the JOG REV function set any of the multi-function input terminals S1 to S6 to 7.
- Jog acceleration time (00-19) is the time required to accelerate from 0 to 100% of maximum output frequency.
- Jog deceleration time (00-20) is the time required to decelerate from 100 to 0% of maximum output frequency.
- Maximum frequency is set by parameter 01-02.
- The inverter uses the Jog frequency (00-18, default 6.0 Hz) as its frequency reference when jog is active.