4-69
Example 2:
Automatic operation mode
– Continuous cycle
In this example the inverter repeats the same cycle.
Parameter Settings:
06-00 =
2 or 5 (Continuous cycle operation)
06-01~06-47= Enter same setting as that of Example 1.
05-01
06-01
06-02
06-03
05-01
06-01
06-02
06-03
06-16
06-17
06-18
06-19
06-16
06-17
06-18
06-19
T
Hz
RUN
Command
RUN
ON
S1 to S6 auto
Run enable
Example 3:
Automatic operation mode
– Single cycle and continue running at last speed of the cycle
In this example the inverter executes a single cycle and continue running at last speed of the cycle.
Parameter Settings:
06-00=
3 or 6 (Single cycle operation)
06-32~06-35=
1 (Forward)
06-36~06-47=
0
Other parameter =
Enter same setting as that of Example 1.
05-01
06-01
06-02
06-16
06-17
06-18
06-31
Hz
06-15
T
RUN
Command
RUN
RUN
S1 to S6 auto run
enable