9-3
Commonly used PID control modes
1:
Forward operation: PID operation enabled, motor speeds increases when feedback signal is smaller than
set-point (most fan and pump applications)
3:
Reverse operation: PID operation enabled, motor slows down when feedback signal is smaller than set-point
(e.g. level control applications)
To set parameter 10-03:
- After power-up press the
MODE
key
- Select 10-03 using the arrow keys and up/down keys
- Press
</ENTER
key
- Set parameter 10-03 using the arrow keys and
</ENTER
key to save setting.
Important:
To use the PID function parameter 00-05 (Main Frequency Source Selection) has to be set to 6 for
PID reference.
9.2 Connect Transducer Feedback Signal (10-01)
The PID function in the inverter
Depending on the type of feedback transducer used, the inverter can be setup for either 0-10V or a 4-20mA
feedback transducer.
Feedback Signal 4
– 20mA (10-01 = 2)
24V
AI1
AGND
R1A
R1B
10V
AO
R2B
R2B
COM
S1
S3
S5
SF
AI2
R1C
S2
S4
S6
SG
4
– 20mA
+
-
Analog Input AI2
Common, GND
Control Terminals /
User Terminals
Set jumper JP3
to position1 & 2
JP3
1
2
3