background image

3.17  Traps
3.18  When to Use a Liquid Trap
 

When pumping gases or low vapor loads, a trap is not necessary unless you want to capture 
vapors evolved from the process. When a heavy load of water or organic vapor is evolved from 
the vacuum process, condensation of vapor in the pump mechanism may occur. The reason 
is the pump is compressing the vapor as it passes through the pump. If the vapor is dense 
enough, the compression will cause condensation of the vapor in the pump mechanism. The 

valve system in the pump mechanism is designed to pass the small quantity of liquefi ed vapor 
formed when pumping heavy vapor loads. The liquid formed will be ejected from the exhaust 
port. The ejected liquid from the exhaust port can either be collected in a liquid trap attached 
to the exhaust port or the vapor trapped in a cold trap placed in-line between the pump and 
the vacuum chamber. A simple, inexpensive liquid trap can be made from a fi ltering fl ask. The 
fi ltering fl ask is connected by 3/8”ID hose to the exhaust port by using the loose hose barb 
provided. 

3.19  When to Use a Cold Trap
 

The use of a cold trap when pumping heavy vapor loads will eliminate the need for a liquid 
trap attached to the exhaust port. The cold trap is installed between the pump and the vacuum 
chamber. The water or organic vapors evolved from the vacuum process will upon entering 
the cold trap will come in contact with the surfaces of the trap and condense. Commonly used 
refrigerants are liquid nitrogen or dry ice with alcohol slurry. Dry ice provides suffi cient cooling 
to freeze out most heavy water vapor loads. A variety of cold traps are available from Welch. 
Please call our customer service department. For additional information at (847) 676-8800.

3.20  The Care of a Liquid Trap
 

A liquid trap needs no refrigerant. The key maintenance issue when pumping high vapor loads 
is to regularly drain the trap of liquid ejected from the dry vacuum pump.

3.21  The Care of a Cold Trap
 

When using a cold trap the refrigerant should be maintained at a high level in the fl ask to keep 
the trap at a uniformly low temperature. If the trap is rewarmed it may allow re-evaporation of 
the condensate. The refrigerant add tube on the liquid nitrogen trap should not be obstructed 
as the refrigerant boil-off can produce dangerously high pressures. If the trap becomes 
saturated it should be disconnected from the system, drained and cleaned. An increase in 
pressure in the vacuum system will normally indicate that the trap has become saturated. 
To clean the trap, remove the trap from the system and allow the trap to warm up and rinse 
off the condensate with a suitable solvent in a fume hood. Thoroughly clean and dry the trap 
before reinstalling into the system. If a liquid nitrogen trap is used, the refrigerant add tube 
on the liquid nitrogen trap should not be obstructed as the refrigerant boil-off can produce 
dangerously high pressures.

8

Summary of Contents for 2019B

Page 1: ...ng the pump See Section 3 15 CAUTION Do not pump liquids with the pump Pumping liquids will cause the pump to stop working Part No 642913 Printed in USA WELCH ILMVAC Welch Ilmvac 5621 W Howard Street...

Page 2: ...ons are found where failure to observe the instruction could result in damage to the equipment associated equipment and process These units conform to the SI International system of units of measureme...

Page 3: ...ump location 6 3 15 Discharge provisions 7 3 16 Electrical power 7 3 17 Traps 8 3 18 When to Use a liquid Trap 8 3 19 When to Use a cold Trap 8 3 20 The care of a liquid trap 8 3 21 The care of a cold...

Page 4: ...en the protector resets Always disconnect power source before servicing 1 15 Never drop or insert ngers or any other object into any openings 1 16 Do not operate this product where oxygen is being adm...

Page 5: ...re 1 41 Do not use this pump in or near explosive atmospheres or where aerosol spray products are being used 1 42 Do not use this product near ames WARNING Failure to observe the above safety precauti...

Page 6: ...ervice Support on www welchvacuum com 3 13 Pump Mounting Rubber feet are attached to the pump casing 3 14 Pump Location WARNING Don t operate this pump in an atmosphere containing ammable or explosive...

Page 7: ...Intake Hose barb tting 1 4 NPT x 3 8 ID hose 3 16 Electrical Power 3 16 1 Power Source Review Review the power source and the motor rating to be sure they agree in voltage phase and frequency Serious...

Page 8: ...he cold trap will come in contact with the surfaces of the trap and condense Commonly used refrigerants are liquid nitrogen or dry ice with alcohol slurry Dry ice provides suf cient cooling to freeze...

Page 9: ...he system and painting the suspected area with a thick soap solution Escaping air will produce soap bubbles 4 13 Operating Pressure Range Vacuum pumps are designed to be run from slightly below atmosp...

Page 10: ...emove head set head with screws aside for assembly 5 Remove four screws 2 from valve plate Remove valve plate and set aside for reassembly 6 Remove diaphragm liner and discard Reassembling the diaphra...

Page 11: ...n with each rotation of the fan If you don t feel suction or if you feel or hear a thump as you turn the fan DO NOT CONNECT THE UNIT TO A POWER SOURCE review the assembly procedure for possible error...

Page 12: ...Description 2019K 01 2019K 03 2500K 04 1 Diaphragm Buna N 1 1 2 Diaphragm liner PTFE 1 1 3 Diaphragm Hold Down Plate 1 4 Valve Plate Assembly 5 O Ring Gasket Head 1 6 Pump Head Assembly Includes item...

Page 13: ...d however short will be repaired under this warranty rather than replaced The warranty is effective for one year from the date of original purchase when 1 The warranty card has been completed and retu...

Page 14: ...L 60714 Phone 847 676 8800 Technical Support Fax 847 677 8606 E Mail gdwelchvacuum gardnerdenver com Web Page www welchvacuum com Copyright 1997 2007 Gardner Denver Welch Vacuum Technology Inc Welch i...

Reviews: