WMS-100 104193 V2.7 - 14.10.2019
Operating voltage
230V AC +/-10%, 50 Hz
Relay contacts
10 make-contacts
max. switching current
8 x each 10A AC1 - 250V AC
2 x each 16A AC1 - 250V AC
max. switching voltage
250V AC - 50..60 Hz
Display
13 mm LED - Display, 3 digits
LED switching status displays 3 mm
Display range
-99 .. 999
Sensor type
KTY 81-210
Sensor cable lenght
2 metres (or as required)
Measurement range
-5° .. +70°C
Temperature resolution
0,1°C
Level detection
via 2 electrodes (optional)
Digital inputs
6 (via opto coupler)
Connection
Plug-in screw connections
for cables up to 2.5 mm²
Housing
FEG 106/175 M
- front dimension
106 x 175 mm
- front panel cut out
156 x 96 mm
- insertion depht
45 mm
Protection (housing front)
IP 64
Environment specifications:
- Operation temperature
0° .. +50°C
- Storage temperature
-20° .. +70°C
- max. humidity
75% (no dew)
Technical Data
40 mm
6,0 mm
6,1 mm
Sensors other than our standard type are available on request
(different bush from or cable length).
Some of the options are shown here.
Sensor dimensions and technical data
Sensor element
Bush material
Bush length
Bush diameter
Cable material
Measurement range
Cable lenght
Protection type
KTY sensor
1.4301(V2A)
40 mm
6.0 mm +/- 0.1
PVC
-10 .. 70° C
Standard 2 metres
IP 65
Technical data subject to changes.
Page 8