![Weishaupt W-FM 25 Manual Download Page 66](http://html.mh-extra.com/html/weishaupt/w-fm-25/w-fm-25_manual_953369066.webp)
9 Technical documentation
9.1 Program sequence
Display
Operating phase Condition
F ..
00
Fault present
OFFUPr
UPrGAS
UPrOIL
01
Waiting in unprogrammed condition
OFF
OFFGAS
OFFOIL
02
Waiting for heat demand
1
03
Extraneous light check
2
04
Shutdown check air pressure switch
05
Initialisation W-FM
06
Waiting for start release
07
Internal sequence
08
Driving air damper actuator to pre-purge
3
09
Waiting for speed standardisation confirmation
10
Start burner motor
11
Waiting for air pressure
4
12
Pre-purge
13
Internal sequence
5
14
Driving to ignition position
6
15
Gas pressure check on low / valve proving gas pressure switch
16
Pre-ignition
7
17
First safety time - fuel release
18
First safety time - flame detection
8
19
First stabilisation time
20
Stop setting mode: P0 -A
21
Second safety time
22
Second stabilisation time
23
End setting mode: P0 -B
9
24
Driving to partial load
10
25
Operation (load control is activated)
15
26
Internal sequence
27
Driving to partial load
28
Fuel valves close
29
Internal sequence
30
Start post burn time / post-purge
31
Post-purge contact dependent (X3:14)
32
Post burn time
16
33
Restart interlock
11
34
Valve proving - vent valve interspace
12
35
Valve proving - test time valve 1
36
Internal sequence
13
37
Valve proving - fill valve interspace
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
9 Technical documentation
83294002 • 2/2014-11 • La
66-70
Summary of Contents for W-FM 25
Page 71: ...83294002 2 2014 11 La ...