6.2 Gas burner with speed control
1. Preset combustion manager
▶
Unplug plug No. 7 from combustion manager.
▶
Switch on voltage supply.
✓
The unprogrammed condition of the combustion manager is indicated by a flashing
display.
The burner goes to lockout.
▶
Press [ENTER] key.
✓
Burner has been reset.
✓
Combustion manager drives to Standby.
Parameter
A
must be set to value
2
.
▶
Press [Enter] and [+] keys simultaneously for approx. 2 seconds.
✓
The parameter level is activated.
▶
Press [+].
▶
Press [Enter] key until parameter
A
is displayed.
▶
Set parameter
A
to value
2
(without low gas pressure switch).
▶
Press [Enter] key until parameter
OFFUPr
is displayed again.
▶
Press [G] and [L/A] simultaneously.
✓
Combustion manager changes to access level.
▶
Press [+].
✓
Setting level (parameter
E0
) is displayed.
▶
Adopt value
0
(single fuel burner), if necessary adjust using [ENTER] and [-] key.