Pno. Information
Range of values
Factory
setting
d
Flame sensor
0
= Ionisation electrode / flame sensor FLW
1
= switch input (X3:14)
2
= flame sensor QRB
0
E
Display mode
On
= Parameter E0 … E4 not activated in setting mode
OFF
= Parameter E0 … E4 activated in setting mode
On
(2
F
Restart attempts following
flame failure
0
…
1
1
(2
Following commissioning, set parameter
E
to
OFF
.
After parameter
F
or a waiting time of approx. 20 seconds the combustion manager
changes over to the operating level.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
4 Operation
83294002 • 2/2014-11 • La
27-70