Fault code
Cause
Rectification
CEh
Bridging plug No. 15 is missing
▶
Plug in bridging plug
High gas pressure switch does not switch
▶
Check gas connection pressure
▶
Set gas pressure switch
▶
Check gas pressure switch
CFh
No start release (X3:14)
▶
Check start release
d0h
Fuel change-over during ignition phase
▶
Check fuel change-over
d1h
Connection to actuator faulty
▶
Check the connection
Coded plug on actuator slot missing
▶
Plug in coded plug
d2h
More than 5 resets in the last 15 minutes by re-
mote reset (X3:14)
▶
Rectify cause of fault
▶
Carry out reset using operating panel (AM)
Installation and operating instruction