Value maximum (KNX)
KNX value, which corresponds to
Value maximum (register)
.
The conversion is always transferred to the entire register area.
Value minimum/maximum (register) defines no limits.
Function (for
“KNX to Modbus” and “Double word register”)
This parameter defines the transmission mode of the double word register. The following options
are available:
▪
Write multi holding registers
– 16
Both word registers in one request
▪
Write single holding register
– 06
For each word register one request
As “Modbus master”, with “Modbus to KNX” and “Double word register”, multi read
requests should be activated in order to read both word registers in one request.
Address
(for “Double word register”)
Double word registers use the register address specified here as well as this register a 1.