© 2020 Weinzierl Engineering GmbH
Page 25/49
Value minimum (KNX)
KNX value which corresponds to
Value minimum (register)
.
Value maximum (KNX)
KNX value, which corresponds to
Value maximum (register)
.
The conversion is always transferred to the entire register area.
Value minimum/maximum (register) defines no limits.
5.8
Channel function “DPT 05 – configured – 1 byte”
Type
The following types are configurable:
▪
Bit register
1 byte configured value (KNX) sets bit register (Modbus)
▪
Bit in word register
1 byte configured value (KNX) sets 1 bit in word register (Modbus)
▪
Value in word register
1 byte configured value (KNX) is mapped to value in word register (Modbus)
5.8.1 Type
– Bit register
5.8.1.1 Direction
– KNX to Modbus
Value (object)
This parameter defines the value for which the group object (KNX) is checked.