•OutputtypeSelectionandCalibration
AnalogueOutputSetup
The analogue output type can be set by the position of two push-fit
jumpers on J1 and J2 of the analogue output board. The analogue
output board runs along the center of the main PCB and at right angles
to it.
• For Voltage outputs, connect the jumpers across J1 and J2.
• For current outputs, fit the jumpers to one post only.
AnalogueOutputCalibration
Equipmentrequirements
• An accurate digital multimeter (accurate to 0.0 mV and ±0.1 μA)
TerminalConnectionsforoutputcalibration
CalibrationStage
Signaltype
Terminal
Analogue Output
Current/Voltage
3
Current/Voltage output −
4