40
Whenthe
displayshows
Action/Description
Put the instrument in setup mode and scroll through the main menu
C Pn
Press
ì
or
Å
C Py
Press
ENT
to select input calibration
InLO
Set the signal source to the lowest value in the required range.
Wait a few seconds (for the signal to stabilise) and press
ENT
InLO
Display will stop flashing (for about 20 s) to show that the instrument is processing
the input.
InHI
Set the signal source to the Highest value in the required range.
Wait a few seconds (for the signal to stabilise) and press
ENT
InHI
Display will stop flashing (for about 10 s) to show that the instrument is processing
the input.
COPn
Continue with the setup sequence.
Note: To discard changes to calibration and setup you can remove the power at this point.
Move about 1 mm
1. Gently move lug out a fraction with a screwdriver to release the
backplate.
2. Pull the backplate back slightly to keep lug from clicking back into
place.
. Repeat with each lug until backplate comes loose.
AnalogueInputCalibration