Note : The OK LED will generally not light continuously unless the cable is in place and the
configuration software is running.
5.3.1
Read Inputs
This option provides a display of the
measured input signals in the WI-I/O K,
both internal and external. Digital inputs
(internal and external) are displayed as
"ON" or "OFF", the pulse input
accumulated count values are displayed
and the analog input value is displayed in
mA or V.
The displayed values will only update
when you select the “Update” box. Note
that the analog input value is only updated
when the configured analog sample
occurs.
If the analog display shows mA and you are using a voltage signal, then the analog input has not
been calibrated. Select the “…” box beside the analog display and follow the procedure in 5.3.3
Unit WI-I/O 9-K