User Manual v1.9
Manual
WI-I/O 9-K
v1.9
Page 39
4.6
Supply Voltage
The supply voltage may be mapped as an internal analog input. The 16 bit value corresponds to
0-30V. There is no analog sensitivity for this measurement - it is only transmitted based on the
configured update time. The measurement is taken every time the WI-I/O K transmitter operates.
The supply voltage also has user-configurable setpoints to determine the Supply Low Volts
alarm. These setpoints can be set from the SetPoint option. The WI-I/O K module will shut-
down when the supply voltage reaches 90% of the “low volts” value. We recommend the
following setpoint values:
Battery Type
Low Volts Setpoint
Shut-down Voltage
WI-BP-I/O-9-K Battery Pack
6.0
5.4
12V “Gell-cell”
11.2
10.0