background image

 Bedienungsanleitung 

3

  User guide 

37

  ユーザガイド 

71

1238120000 Transclinic 8i+

1238130000 Transclinic 14i+

Weidmüller Interface GmbH & Co. KG

Klingenbergstraße 16

D-32758 Detmold

T   +49 (0) 5231 14-0

F  +49 (0) 5231 14-292083

[email protected]

www.weidmueller.com

R.T.Nr. 1485580000/04/11.16

Summary of Contents for Transclinic 14i+

Page 1: ...7 71 1238120000 Transclinic 8i 1238130000 Transclinic 14i Weidm ller Interface GmbH Co KG Klingenbergstra e 16 D 32758 Detmold T 49 0 5231 14 0 F 49 0 5231 14 292083 info weidmueller com www weidmuell...

Page 2: ......

Page 3: ...10 3 Installation 11 3 1 Installationsanforderungen 12 3 2 Anschluss der PV Strings 14 3 3 Anschluss der digitalen Eing nge 18 3 4 Anschluss der Versorgungsspannung 20 3 5 Anschluss der RS 485 Ports...

Page 4: ...MW einige befinden sich in den hei en und staubigen W sten Afrikas und Indiens einige sind der feuchten und salzigen Luft der s dost asiatischen K sten ausgesetzt andere befinden sich in den k lteste...

Page 5: ...s Transclinic misst Str me anhand von redundanten hoch stabilen Strommesswiderst nden auch Shunts genannt Shunts bieten im Vergleich zu anderen Strommessverfahren ein sehr lineares und berechenbares V...

Page 6: ...potentiellen Folgen aufgelistet GEFAHR Zeigt an dass die Folge bei Nicht Beachten der Warnhinweise Tod oder schwere Verletzungen sind WARNUNG Zeigt an dass eine m gliche Folge bei Nicht Beachten der...

Page 7: ...des Ger tes f hren Diese Verwendungen f hren zu einem sofortigen Erl schen jeglicher Garantie und Gew hrleistungsanspr che des Bedieners gegen ber dem Hersteller GEFAHR Dies ist ein industrielles Prod...

Page 8: ...zwei digitale Eing nge Die Messwerte k nnen via RS 485 Kabel von einem ModBus RTU Client abgefragt werden Die pr zisen Messungen dieses Ger ts haben unterschiedlichen Nutzen Die folgende Liste ist dah...

Page 9: ...liminiert werden bevor es zu einem Brand kommt Priorisierte Instandhaltung Durch Kombination aller Messungen kann das Wartungspersonal besser entscheiden welche DC seitigen Arbeiten auf Grund eines Le...

Page 10: ...gelten die allgemeinen Verkaufsbedingungen von Weidm ller in ihrem jeweils g ltigen Stand nderungen vorbehalten 2 5 Kontakt Bitte kontaktieren Sie Ihre lokale Weidm ller Vertriebsgesellschaft f r weit...

Page 11: ...atur 5 C bis 40 C Maximale relative Luftfeuchte 80 bei Temperaturen bis 31 C linear sinkend bis 50 relative Luftfeuchte bei 40 C GEFAHR W hrend der Installation Verdrahtung Konfiguration Instandhaltun...

Page 12: ...r Besch digung Thermische Installationsvoraussetzungen Dieses Produkt ben tigt keine erzwungene Konvektion z B Ventilator um zuverl ssig zu arbeiten Die Orientierung der Leiterplatte muss nach der Ins...

Page 13: ...2 D D C IN2 Negative String Eing nge X1 X2 X4 X3 X5 X7 RS 485 X6 SW1 SW2 Negative Kupfer schiene PV strings Wechselrichter Digitale Eing nge Transclinic 8i RS 485 D D C 24 V Lasttrennschalter Sicherun...

Page 14: ...hrleistet sein Die empfohlene L sung ist die nahe und leicht zug ngliche Installation typischer Weise innerhalb des GAKs der folgenden Ger te Sicherungstrennschalter elektrische Platzierung zwischen...

Page 15: ...clinic ausge bt wird Bei Nicht Beachten dieser Anforderungen kann die Gefahr eines Feuers oder elektrischen Schlags entstehen und das Produkt besch digt werden Die folgende Tabelle fast alle Anforderu...

Page 16: ...n drahtig 12 mm 12 mm Drehmoment 4 5 Nm 1 2 1 5 Nm 1 2 1 5 Nm Ben tigte Werkzeuge Drehmoment schrauber 10 mm ISO hex Kopf Drehmoment schrauber 1 5 5 mm Flachklinge Drehmoment schrauber 1 5 5 mm Flachk...

Page 17: ...swahl der Kabelschuhe muss auf ausreichend Kontaktfl che zwischen dem Kabelschuh und der Kupferschiene geachtet werden Des Weiteren darf der Kabelschuh die verbleibenden Muttern nicht ber hren keine K...

Page 18: ...d oder X4 an um Spannungsmesswerte zu erhalten 3 3 Anschluss der digitalen Eing nge Die digitalen Eing nge dieses Ger ts sind potentialfrei hinsichtlich des Rests der Schaltung Dies wird durch daf r b...

Page 19: ...en tigte externe Isolation funktional WARNUNG Die Anschlussleitungen der digitalen Eing nge m ssen eine ausreichende L nge haben damit keine mechanische Belastung auf das Transclinic ausge bt wird Bei...

Page 20: ...nnten und geeigneten Spannungsquelle versorgt werden Normalerweise wird diese Versorgung innerhalb des GAKs installiert Dies sind die empfohlenen Weidm ller Netzteile 8739140000 CP SNT 48W 24V 2A 8951...

Page 21: ...ne Netzteil einen Ausgangsstrom 2 5 Adc hat sollte ein berstromschutz typisch Sicherung zwischen dem Netzteil und diesem Ger t installiert werden ACHTUNG Falls das Netzteil au erhalb des GAKs installi...

Page 22: ...geeigneten Fachkr ften durchgef hrt werden Diese Bedienungsanleitung dient nicht als Ersatz f r Erfahrungen in der Feldbusverdrahtung und Weidm ller kann nicht f r aus unsachgem er Verdrahtung result...

Page 23: ...intern parallele RS 485 Ports Anschluss X5 und X7 Die Pins dieser Anschl sse sind mit D D und C markiert ACHTUNG Dieses Ger t hat zwei RS 485 Anschl sse X5 und X7 um mehr als ein Transclinic in einem...

Page 24: ...cada Software oder das Programm im PLC Datenlogger ist ein client aus Sicht des ModBus Ein RS 485 Ethernet Konverter oder die Hardware eines PLC Datenloggers ist ein master aus Sicht des RS 485 Richtl...

Page 25: ...Anschluss irgendeines GAK an zu schlie en a Der durchgeschleifte Schirm l uft vom Anfang bis zum Ende des RS 485 Bus Lassen Sie den Schirm am entferntesten Punkt z B bezogen auf die Leitungsl nge des...

Page 26: ...G Die RS 485 Leitung muss eine ausreichende L nge haben damit keine mechanische Belastung auf das Transclinic ausge bt wird Bei Nicht Beachten dieser Anforderungen kann die Gefahr eines elektrischen S...

Page 27: ...clinic RS 485 slave D D C RS 485 master D D Transclinic RS 485 slave D D C Transclinic RS 485 slave D D C Transclinic RS 485 slave D D C RS 485 master D D Transclinic RS 485 slave D D C a durchgeschle...

Page 28: ...Tabelle zeigt die bin re Kodierung der ModBus Adressen anhand der DIP Schalter Die werksseitig eingestellte slave Adresse ist 1 SW 1 1 on und SW1 2 SW 1 8 off Als Beispiel ist die Modbus Adresse 175 g...

Page 29: ...nternen Verwendung muss in der Einstellung off bleiben Werkseinstellung NOTIZ Alle Ger te eines RS 485 Bus m ssen die gleichen seriellen Einstellungen haben und jede ModBus Adresse darf nur einmal ver...

Page 30: ...ft f r weitere Informationen 1 x RS 485 0 C bis 60 C 1242080000 IE CS 2TX 1RS232 485 1 x RS 485 40 C bis 75 C 1285830000 IE CST 2TX 1RS232 485 2 x RS 485 0 C bis 60 C 1242090000 IE CS 2TX 2RS232 485 2...

Page 31: ...ies ist ein guter Mittelwert zwischen unn tigem Netzwerkverkehr der Monitoring Datenbankgr e und der Zeitaufl sung Bitte beachten Sie dass weder die Sonne die Wolken noch der MPP des Wechselrichters s...

Page 32: ...te verk rzen Sie die Wartungsintervalle in sehr verschmutzter staubiger Umgebung und bei gro en Temperaturschwankungen durchgef hrt werden m ssen sind Kontrollieren Sie das Drehmoment von X1 X4 X2 und...

Page 33: ...es Produkt darf nur von Weidm ller gewartet werden Bei Nicht Beachten erlischt die Garantie und f hrt zu gef hrlichen Situationen Bitte kontaktieren Sie Ihre Weidm ller Vertriebsgesellschaft f r Servi...

Page 34: ...rgungsstrom 70 mAdc im stabilen Zustand 200 mAdc max Betriebstemperaturbereich 20 C bis 70 C Relative Luftfeuchtigkeit 5 bis 95 nicht kondensierend Kommunikationsprotokoll Modbus RTU ber RS 485 Anzahl...

Page 35: ...s haben Sie das Recht es nach dem Ende seines Lebenszyklus kostenfrei an Weidm ller zur ck zu senden Weidm ller wird dann Ihr Ger t nach der aktuellen Gesetzeslage fachgerecht recyceln und entsorgen E...

Page 36: ...able Logic Controller Programmierbarer Logik Controller PV Photovoltaik RF RadioFrequency Funkfrequenz RS 485 TIA EIA 485 A Electrical characteristics of generators and receivers for use in balanced m...

Page 37: ...r contact details 44 3 Installation 45 3 1 Mounting requirements 46 3 2 Wiring of PV inputs 48 3 3 Wiring of digital inputs 52 3 4 Wiring of the power supply input 54 3 5 Wiring of RS 485 ports 56 3 6...

Page 38: ...00 MW in size some are located in the hot and dusty deserts of Africa and India some plants are near the humid and salty tropical beaches of Southeast Asia some are in the coldest continental areas th...

Page 39: ...of redundant high stability current sensing resistors also known as shunts Shunts offer a very linear and predictable response not subject to hysteresis offsets overload offsets and other defects fou...

Page 40: ...rd DANGER Indicates that death or severe personal injury will result if the relevant information is not taken into account WARNING Indicates that death or severe personal injury may result if the rele...

Page 41: ...ng so will automatically void the warranty and any claims from the customer against Weidm ller DANGER This is an industrial equipment meant to be installed operated maintained and troubleshot by skill...

Page 42: ...rature and two digital inputs The measured values can be accessed from a Modbus RTU client typically a Scada or a PLC via a RS 485 cable The accurate measurements performed by this device have multipl...

Page 43: ...edied before it becomes a fire accident Prioritizing maintenance actions by combining all the measurements above the maintenance staff can better decide what tasks in the DC side have higher priority...

Page 44: ...e apply in their respective valid form The equipment specifications and the contents of this user guide are subject to change without notice 2 5 Manufacturer contact details Please contact your local...

Page 45: ...um relative humidity 80 for temperatures up to 31 C decreasing linearly to 50 at 40 C DANGER During mounting wiring configuration maintenance and troubleshooting of this equipment there shall be no li...

Page 46: ...there is no realistic risk of damaging it due to external impacts Thermal considerations This product does not need forced convection i e a fan to operate reliably The mounting orientation shall ensur...

Page 47: ...IN1 24 V 0 V IN2 D D C IN2 negative PV inputs X1 X2 X4 X3 X5 X7 RS 485 X6 SW1 SW2 negative copper busbars PV strings inverter digital inputs Transclinic 8i RS 485 D D C 24 V switch disconnector fuses...

Page 48: ...equirement creates an electrical shock hazard The recommended solution is to install the following devices easily accessible and near this equipment typically inside the combiner box fuse disconnector...

Page 49: ...not apply a mechanical strain to this equipment Failure to observe this requirement creates fire and electrical shock hazards and may also damage this equipment The following table summarizes the requ...

Page 50: ...m Tightening torque 4 5 Nm 1 2 1 5 Nm 1 2 1 5 Nm Required tool torque wrench with 10 mm ISO hex head torque wrench with 1 5 5 mm flat blade torque wrench with 1 5 5 mm flat blade External insulation r...

Page 51: ...ween the negative copper busbar and the lug moreover the cable lug shall not contact the non hex nuts of the negative copper busbars do not use lugs wider than 15 mm Failure to observe these requireme...

Page 52: ...edicated optocouplers which provide a double insulation barrier between the digital inputs and the PV side terminals From the user perspective this means digital inputs without ground loops and full s...

Page 53: ...ut cables shall have the right length so that they do not apply a mechanical strain to this equipment Failure to observe this requirement creates an electrical shock hazard and may also damage this eq...

Page 54: ...ansclinic resides These are the recommended Weidm ller power supplies 8739140000 CP SNT 48W 24V 2A 8951330000 CP M SNT 70W 24V 3A CAUTION This equipment is marked with the DC symbol because it is fed...

Page 55: ...ide the combiner box then it is mandatory to install next to this equipment inside the combiner box a suitable Weidm ller DC surge protective device Please contact your Weidm ller s sales representati...

Page 56: ...hat this step of the equipment installation is performed by staff with the right skills and tools This user guide cannot be a replacement for field bus wiring experience and Weidm ller cannot be made...

Page 57: ...ally paralleled RS 485 ports connectors X5 and X7 The pins of these connectors are marked D D and C CAUTION There are two RS 485 connectors in order to simplify the installation of more than one Trans...

Page 58: ...atalogger is a client from the viewpoint of the Modbus standard A RS 485 to Ethernet converter or the hardware of a PLC datalogger is a master from the viewpoint of the RS 485 standard Guidelines for...

Page 59: ...non stop from end to end of the RS 485 bus Leave the shield floating i e unconnected at the far end of the RS 485 bus i e the combiner box farthest from the RS 485 master in terms of cable length Tie...

Page 60: ...NING The RS 485 cables shall have the right length so that they do not apply a mechanical strain to this equipment Failure to observe this requirement creates an electrical shock hazard and may also d...

Page 61: ...ransclinic RS 485 slave D D C RS 485 master D D C Transclinic RS 485 slave D D C Transclinic RS 485 slave D D C Transclinic RS 485 slave D D C RS 485 master D D C Transclinic RS 485 slave D D C a dais...

Page 62: ...ing of the Modbus device address via DIP switches The factory default slave address is 1 i e SW 1 1 in the on position and SW 1 2 to SW 1 8 in the off position As an example the DIP switch coding for...

Page 63: ...erved for future use must be left in the off position factory default NOTICE All the devices belonging to one RS 485 bus must have the same serial settings and the Modbus device address of each Transc...

Page 64: ...presentative for further information 1 x RS 485 0 C to 60 C 1242080000 IE CS 2TX 1RS232 485 1 x RS 485 40 C to 75 C 1285830000 IE CST 2TX 1RS232 485 2 x RS 485 0 C to 60 C 1242090000 IE CS 2TX 2RS232...

Page 65: ...seconds This is a good tradeoff between unnecessary network traffic and database size and time resolution Keep in mind that the sun the clouds and the MPP of the inverter do not change significantly i...

Page 66: ...only maintenance tasks required every two years please increase the frequency of maintenance sessions if the device operates in very polluted dusty environment and or is frequently subject to large t...

Page 67: ...is product can only be serviced by Weidm ller Failure to observe this requirement voids the warranty and can lead to dangerous situations Please contact your Weidm ller sales representative for servic...

Page 68: ...dy state 200 mAdc max Operating temperature range 20 C to 70 C Operating relative humidity range 5 to 95 non condensing Communications protocol Modbus RTU over RS 485 serial line Number of digital inp...

Page 69: ...u the right to return it to Weidm ller free of charge at the end of its service life Weidm ller will then professionally recycle and dispose of your device in accordance with the applicable laws Elect...

Page 70: ...in balanced multipoint systems SPD Surge Protective Device Annex B Modbus register table located at the very end of the user guide Notes As defined in the Modbus standard the register addresses shown...

Page 71: ...71 0 72 1 72 2 74 2 1 74 2 2 75 2 3 76 2 4 78 2 5 78 3 79 3 1 80 3 2 PV 82 3 3 86 3 4 88 3 5 RS485 90 3 6 DIP 96 4 Modbus RTU 98 5 100 6 102 Annex A 104 Annex B Modbus 104...

Page 72: ...72 0 2011 3 2011 5 2 2012 3 3 2013 10 4 2016 11 5 1 Transclinic PV DC Transclinic 5 PV Transclinic 100MW PV Transclinic...

Page 73: ...73 PV Transclinic Transclinic 3GW Transclinic PV Transclinic PV EMC Transclinic 2 Transclinic 9 Transclinic IEC EN EU EMC Transclinic RS 485 Modbus SCADA PLC Transclinic 3 1...

Page 74: ...74 2 2 1...

Page 75: ...75 2 2 ISO 7000 0434B X1 X4 X2...

Page 76: ...76 X1 X4 X1 X4 X2 15 2 3 Transclinic DC 2 PV Modbus RTU SCADA PLC RS485 0 P DC 0 PV...

Page 77: ...77 DC IEC61724 SPD Transclinic Modbus SPD ON OFF OFF Transclinic DC SCADA DC Transclinic PV DC Transclinic...

Page 78: ...78 2 4 2 5 Weidm ller Interface GmbH Co KG Klingenbergstra e 16 32758 Detmold Germany 49 5231140 49 523114 292083 info weidmueller com...

Page 79: ...79 3 DIP 5 40 80 31 50 40 PV 1 kV...

Page 80: ...80 3 1 IEC 61439 2 PV EN50022 DIN TS35 DIN IEC62208 IEC60529 IP54 IEC 62262 Transclinic IK 09 30 20 70 PV IEC TR 60890...

Page 81: ...6 6 6 6 6 6 6 6 1 1 9 9 1 1 QHJDWLYH 39 LQSXWV 56 6 6 QHJDWLYH FRSSHU EXVEDUV 39 VWULQJV LQYHUWHU GLJLWDO LQSXWV 7UDQVFOLQLF L 56 9 VZLWFK GLVFRQQHFWRU IXVHV IXVHV SRVLWLYH 39 LQSXW 63 7UDQVFOLQLF L...

Page 82: ...82 3 2 PV PV X1 X4 X2 2 X1 X4 PV PV X2 PV PV PV PCS DC PV IEC 60947 DC 21B PCS...

Page 83: ...83 PV Transclinic X1 X4 X2...

Page 84: ...0 mm2 2 5 6 mm2 10 35 mm2 2 5 16 mm2 2 5 16 mm2 Transclinic 8i 30A Transclinic 14i 20A 4 35 mm2 PV1 F 6 mm2 PV1 F 12 mm 12 mm 4 5 Nm 1 2 1 5 Nm 1 2 1 5 Nm 10 mm ISO 1 5 5 mm 1 5 5 mm X1 X4 PV X1 X4 2...

Page 85: ...A9 M6 15 15 mm CLC TS50539 12 2010 DC SPD 1351270000 VPU II 3 PV 1000V DC 1351290000 VPU II 3 R PV 1000V DC 1351340000 VPU II 2 PV 600V DC 1351370000 VPU II 2 R PV 600V DC 1351520000 VPU I 2 0 PV 600...

Page 86: ...86 PV PV X2 PV X2 2 1 PV X1 X4 3 3 X3 PV 0 0 Vdc 1 24 Vdc 2 X3 Transclinic 24 Vdc X3...

Page 87: ...87 X3 0 2 2 5 mm2 0 2 4 mm2 7 mm 0 4 0 5 Nm 0 6 3 5 mm Transclinic X3 EMC 3m...

Page 88: ...88 3 4 X6 DC DC PV DC24V Transclinic 8739140000 CP SNT 48W 24V 2A 8951330000 CP M SNT 70W 24V 3A DC DC X6 0 2 2 5 mm2 0 2 4 mm2 7 mm 0 4 0 5 Nm 0 6 3 5 mm...

Page 89: ...89 Transclinic 2 5 Adc DC DC X6 EMC 3m...

Page 90: ...90 3 5 RS 485 X5 X7 RS 485 Modbus Transclinic Transclinic RS 485 RS 485 IC Transclinic RS 485 RS 485 Modbus TIA EIA 485 A TIA TSB 89 A TIA EIA 485 A Modbus v1 1b Modbus v1 02...

Page 91: ...1 X5 X7 0 2 2 5 mm2 0 2 4 mm2 7 mm 0 4 0 5 Nm 0 6 3 5 mm RS 485 DC DC PV Modbus RTU RS 485 RS 485 X5 X7 D D C 2 RS 485 Transclinic X5 X7 RS 485 RS485 RS485 RS 485 IC RS 485 B A D1 D0 D D B A D1 D0 D D...

Page 92: ...er D D C RS 485 2 1 5 3 NG 120 0 2 mm2 AWG24 RS 485 Belden 3106 A Lapp Kabel Unitronic Bus LD 2 2 0 22 Artikelnr 2170204 RS 485 Modbus RTU Transclinic RS 485 Modbus SCADA PLC Modbus PLC RS 485 PV RS 4...

Page 93: ...m PV 400m 120 10 W D D RS 485 RS 485 RS 485 Transclinic 1 UL RS 485 12 k Transclinic RS 485 Transclinic D D 1 2 1 5 C D D C Transclinic C RS 485 C D D 2 C RS 485 RS 485 RS 485 RS 485 RS 485 RS 485 C R...

Page 94: ...94 RS 485 IC C PE RS 485 C Transclinic C RS 485 Transclinic RS 485 SPD RS 485 8924270000 VSPC BASE 2CL FG 8924670000 VSPC RS485 2CH RS 485 C PE FG RS 485 IC...

Page 95: ...95 7UDQVFOLQLF 56 VODYH 7UDQVFOLQLF 56 VODYH 56 PDVWHU 7UDQVFOLQLF 56 VODYH 7UDQVFOLQLF 56 VODYH 7UDQVFOLQLF 56 VODYH 56 PDVWHU 7UDQVFOLQLF 56 VODYH D GDLV FKDLQHG VKLHOG E VHJPHQWHG VKLHOG 56...

Page 96: ...s ID 2 Modbus 1 247 2 00000001 11110111 Modbus RS485 246 PV 1 SW 1 1 ON SW1 2 SW 1 8 OFF Modbus 175 DIP 10 175 2 10101111 SW 1 1 SW 1 2 SW 1 3 SW 1 4 SW 1 5 SW 1 6 SW 1 7 SW 1 8 20 LSB 21 22 23 24 25...

Page 97: ...97 SW 2 RS 485 SW 2 1 ON 9600 bps OFF 19200bps SW 2 2 ON SW 2 3 ON EVEN OFF NONE SW 2 4 OFF 1 RS485 Transclinic Modbus ID ID DIP RS 485 SW2 3 1...

Page 98: ...Modbus Transclinic 2 RS 485 PCS Transclinic Modbus RTU RS 485 SCADA 1242080000 IE CS 2TX 1RS232 485 1 x RS 485 0 60 1285830000 IE CST 2TX 1RS232 485 1 x RS 485 40 75 1242090000 IE CS 2TX 2RS232 485 2...

Page 99: ...99 Modbus RTU RS 485 HUB Transclinic Modbus SCADA PLC Modbus 1 20 PCS MPP 20 PV Tran sclinic Modbus 1 0x04 read input registers 1 35 0x02...

Page 100: ...100 5 OFF Transclinic OFF OFF 15 5 40 31 80 40 50 PV 2 1 X1 X4 X2 DIN RS 485...

Page 101: ...101...

Page 102: ...dc 20 Adc PV 30 mA 20 mA PV 1 0 FS 100 Vdc 1000 Vdc PV 1 0 V DC 24 Vdc 20 70 mAdc 200 mAdc max 20 70 5 95 RS 485 Modbus RTU 2 LOW 0 0 5 Vdc HIGH 1 15 24 Vdc X1 X4 X2 4 kV 2 2000 m IEC 62262 IK07 2 J 8...

Page 103: ...103 LVD 2006 95 EC EMC 2004 108 EC CE WEEE 012 19 EU WEEE...

Page 104: ...Maximum Power Point MPPT Maximum Power Point Tracker MSB Most Significant Bit PCB Printed Circuit Board PDU Protocol Data Unit Modbus frame Modbus PLC Programmable Logic Controller PV Photo Voltaic RF...

Page 105: ...105...

Page 106: ...ent input 05 0 30000 mA AVG_CUR_IN_06 24 Average current input 06 0 30000 mA AVG_CUR_IN_07 25 Average current input 07 0 30000 mA AVG_CUR_IN_08 26 Average current input 08 0 30000 mA AVG_CUR_IN_09 27...

Page 107: ...r unsigned INT 4 input register unsigned INT 4 input register unsigned INT 4 input register unsigned INT 4 input register unsigned INT 4 input register unsigned INT 4 input register unsigned INT 4 inp...

Page 108: ...04 0 30000 Watt AVG_PWR_IN_05 46 Average power input 05 0 30000 Watt AVG_PWR_IN_06 47 Average power input 06 0 30000 Watt AVG_PWR_IN_07 48 Average power input 07 0 30000 Watt AVG_PWR_IN_08 49 Average...

Page 109: ...d INT 4 input register AVG_CUR_IN_05 AV_VOLT_IN unsigned INT 4 input register AVG_CUR_IN_06 AV_VOLT_IN unsigned INT 4 input register AVG_CUR_IN_07 AV_VOLT_IN unsigned INT 4 input register AVG_CUR_IN_0...

Page 110: ......

Reviews: