TROUBLESHOOTING AND MAINTENANCE
Protection/Alarm
Description
Possible causes
A1704:
Slot G high temperature
Temperature in the accessory is high.
- Temperature around the inverter close to 60
◦
C.
F1705:
Slot G overtemperature
Accessory overtemperature.
- Temperature around the inverter above 60
◦
C.
A1706:
Slot G enc. A cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
F1707:
Slot G enc. A cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
A1708:
Slot G enc. B cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
F1709:
Slot G enc. B cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
A1710:
Slot G enc. Z cable
disconnection
Encoder signal Z not detected correctly
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
F1711:
Slot G enc. Z cable
disconnection
Encoder signal Z not detected correctly
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
A1712:
Slot G AI1 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
F1713:
Slot G AI1 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
A1714:
Slot G AI2 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
F1715:
Slot G AI2 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
A1716:
Slot G AI3 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
86 | CFW900