TROUBLESHOOTING AND MAINTENANCE
Protection/Alarm
Description
Possible causes
F1337:
Slot C sensor 3
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
A1338:
Slot C temperature
sensor 4 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
F1339:
Slot C temperature
sensor 4 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
A1340:
Slot C high temperature
in sensor 4
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1341:
Slot C sensor 4
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
A1342:
Slot C temperature
sensor 5 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
F1343:
Slot C temperature
sensor 5 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
A1344:
Slot C high temperature
in sensor 5
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1345:
Slot C sensor 5
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
A1346:
Slot C temperature
sensor 6 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
F1347:
Slot C temperature
sensor 6 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
A1348:
Slot C high temperature
in sensor 6
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1349:
Slot C sensor 6
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1400:
Slot D incompatible
accessory
Error during accessory firmware update.
Old inverter firmware version.
F1401:
Slot D Initialization Error
It was not possible to initialize a resource required for
the accessory to work.
- Resource already in use by another accessory.
In the case of communication network accessories,
only one accessory of each type of network can be
connected to the inverter at a time.
F1403:
Slot D accessory
connection
Loss of communication with the accessory.
- Above-supported electromagnetic noise.
- Vibration above supported limits causing connector
problems.
- Corrupted accessory firmware.
76 | CFW900