Installation and Connection
CFW11W | 2-11
Figure 2.13: Grounding points of the UP11
Use the cables with the gauge indicated in Table 2.6 to ground the UP11 power units.
Table 2.7: Grounding cables
Current (A)
Voltage (V)
Duty
Minimum Cross-Section of
the Grounding Cable (mm2)
700
380-480
ND
240
515
HD
150
640
500-690
ND
240
477
HD
150