Technical Specifications
CFW11W | 5-4
Note:
(1)
Steady state rated current in the following conditions:
Ambient temperature: -0 °C to 40 °C (32 °F to 104 °F) - nominal conditions (measured around the
inverter). 40 °C to 45 °C (104 °F to 113°F) - current derating of 2 % for each 1°C (1.8 °F) above 40 °C
(104 °F).
Coolant input temperature: 0 ºC to 40 ºC (32 °F to 104 °F) according to the coolant used. 40 ºC to 45
ºC (104 °F to 113°F) - current derating of 3 % for each 1°C (1.8 °F) above 40 ºC (104 ºF).
Fluid flow: 20 l/min.
Air relative humidity: 5 % to 90 % non- condensing.
Maximum altitude: up to 1000 m (3,300 ft) - nominal conditions. 1000 m to 4000 m (3,300 ft to 13,200
ft) - current derating of 1 % for each 100 m (or 0.3 % each 100 ft) above 1000 m (3,300 ft) of altitude.
2000 m to 4000 m (6,600 ft to 13,200 ft) – maximum voltage derating of 1.1 % for each 100 m (or 0.33
% each 100 ft) above 2000 m (6,600 ft) , maximum altitude up to 4000 m (13,200 ft).
Pollution degree: 2 (according to EN50178 and UL508C), with non-conductive pollution. The
condensation must not cause conduction through the accumulated residues.
(2)
Table 5.1presents only two points of the overload curve (activation time of 1min and 3 s). The complete
IGBT overload curves for Normal and Heavy Duty Cycles are presented next.
(a)
IGBT overload curve for the Normal Duty (ND) cycle
(b)
IGBT overload curve for the Heavy Duty (HD) cycle
Figure 5.1:
IGBTs overload curves
Summary of Contents for CFW-11W
Page 5: ...General Information CFW11W 1 2 Figure 1 2 Block Diagram of the CFW 11W...
Page 6: ...General Information CFW11W 1 3 Figure 1 3 UC 11 Main parts Figure 1 4 UP 11 Main parts...
Page 31: ...Optional Kits CFW11W 4 2...
Page 38: ...Technical Specifications CFW11W 5 7 5 3 MECHANICAL DATA Figure 5 2 UP11 dimensions mm in...
Page 41: ......