Installation and Connection
CFW11W | 2-14
2.6.3.
Emission and Immunity Levels
Table 2.8:
Emission and Immunity Levels
EMC Phenomenon
Basic Standard
Level
Emission:
Mains Terminal Disturbance Voltage
Frequency range: 150 kHz to 30 MHz
IEC/EN61800-3
-
Without external filter:
Category C4.
-
With external filter:
Category C2 or C3.
Electromagnetic Radiation Disturbance
Frequency range: 30 MHz to 1 GHz
Immunity:
Electrostatic Discharge (ESD)
IEC/EN61000-4-2
4 kV for contact discharge and 8 kV for air discharge.
Fast Transient-Burst
IEC/EN61000-4-4
2 kV/5 kHz (coupling capacitor) power input cables.
1 kV/5 kHz control cables.
2 kV/5 kHz (coupling capacitor) motor output cables.
Conduced Radio-Frequency Common Mode
IEC/EN61000-4-6
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz).
Motor input cables, control cables and remote HMI
cables.
Surge Immunity
IEC/EN61000-4-5
1.2/50 µs, 8/20 µs.
1 kV line-to-line coupling.
2 kV line-to-ground coupling.
Radio-Frequency Electromagnetic Field
IEC/EN61000-4-3
80 to 1000 MHz.
10 V/m.
80
% AM (1 kHz).
2.6.4.
External RFI Filters
Use them only when the conducted emission levels C2 or C3 are not according to IEC/EN61800-3. The models
below are manufactured by Epcos.
Table 2.9:
Filters for networks 380-480 V
Inverter Model
Duty
Filter Model
700
ND
B84143-B1000-S20
HD
B84143-B600-S20
1330
ND
B84143-B1600-S20
HD
B84143-B1000-S20
1995
ND
B84143-B2500-S20
HD
B84143-B1600-S20
2660
ND
----
HD
B84143-B2500-S20
3325
ND
----
HD
B84143-B2500-S20
Table 2.10:
Filters for networks 500-690 V
Inverter Model
Duty
Filter Model
640
ND
B84143-B1000-S21
HD
B84143-B600-S21
1216
ND
B84143-B1600-S21
HD
B84143-B1000-S21
1824
ND
B84143-B2500-S21
HD
B84143-B1600-S21
2432
ND
B84143-B2500-S21
HD
B84143-B2500-S21
3040
ND
----
HD
B84143-B2500-S21
Summary of Contents for CFW-11W
Page 5: ...General Information CFW11W 1 2 Figure 1 2 Block Diagram of the CFW 11W...
Page 6: ...General Information CFW11W 1 3 Figure 1 3 UC 11 Main parts Figure 1 4 UP 11 Main parts...
Page 31: ...Optional Kits CFW11W 4 2...
Page 38: ...Technical Specifications CFW11W 5 7 5 3 MECHANICAL DATA Figure 5 2 UP11 dimensions mm in...
Page 41: ......