WeCo Srl Italia
www.wecobatteries.com
4K4 PRO V 1.11 28-9-2021
The BMS will perform a self-restart 4 times every 15 minutes for a period of 24 hours and after the 24 hour period, the BMS will perform a
self-restart every 12 hours for a period of 4 days.
In the case where the current or voltage limit has been exceeded 4 times consecutively, the operator must wait 30 minutes before
pressing the RUN button again.
A reduction of the charging current at the end of charge and end of discharge in addition to a new set up of the voltage range is mandatory
if the installation faces faults as described above.
Single Cell Curve @25°C Degrees 0.5C Charge/Discharge
The charge and discharge current of the inverter MUST be limited according with the maximum current allowed by each battery cluster
configuration as specified in Section 13 of this manual.
The charge and discharge Voltage range of the inverter MUST be limited as per the module maximum values as specified in this manual.