GRANUDOS Touch, control unit
Index: 02
Date modified: 11/06/2019
OI No.: BA SW 010-02 Granudos Touch-Steuereinheit EN SCHW 8.docx
Page 40 of 43
Operation data sheet,
--master copy--
Please copy the blank operation data sheet for additional uses
Settings menu
Factory setting
Setting ranges
Step during commissioning Optimised
during
operation
1 Dosing performance
pH/acid
Date:
Date:
Acid
8 seconds
1-8 seconds
1
Chlorine
15 seconds
1-15 seconds
1
Cycle
30 seconds
30-360 seconds
30
Dosing time limit acid
0
0-100 minutes
5
Dosing time limit chlorine 0
0-100 minutes
5
Manual dosing
Off
Off – On
2 Reserve indication
chlorine
Reserve message
like order
1-150 kg
1
Barrel size
like order
1-150 kg
1
Reserve indication
On
Off - On
3 Reserve indication acid
Reserve message after
20l
1-500l
1
Barrel size
25l
1-500l
1
Reserve indication
On
Off - On
4 Shock cl.
Dosing performance ac
10%
10-100%
1
Dosing performance cl
50%
0-100%
1
5 System
Password
End user
----
0000 – 9999
1
Technician 1
01234
00000 – 99999
1
6 System
Display
Screensaver
20%
12-100%
2
Delay
00:05
00:00 – 23:59
Backlight
75%
24 - 100%
2
7 System
Network
IP-address
192.168.0.1
Gateway
192.168.0.0
Subnet
255.255.255.0
8 Dust extractionC
Flushing interval
12h
0 – 48h
1
Flushing time
5 seconds
0 - 5 seconds
1
Dust extraction
like order
Off – On
9 Buffer tank
Dosing performance ac
10%
10 - 100%
1
Dosing performance cl
50%
50 - 100%
1
Activate buffer tank
like order
Off – On
10 pH Supervision
Alarm low
6.8 pH
6.5 – 7.4 pH
0.05
Alarm high
7.2 pH
6.6 – 7.5 pH
0.05
Delay time
5 minutes
0 – 60 min
Activate pH Supervision like order
Off – On
11 Delay Booster pump
Delay time
30 seconds
0 - 120 sec
5