19
February 1997
Part No. 920160 Rev A
3.5.
FAULT REPORTING, continued
The transaction counter has a range of 00000 - 59999 and then rolls over to 00001. Each
side of the dispenser has a transaction counter. When Option 01 is entered the current trans-
action number for side 1 is shown in the Sale Money Display. The value of side 2 transac-
tion counter (if two fueling points) is shown in the Sale Volume Display. See Figure 3-4.
for an example. Pushing the Totals button while the transaction values are displayed causes
entry into the Fault Code History Display Mode. See Figure 3-5. for an example. As shown
the transaction number is displayed for each side along with the fault code for that transac-
tion number. The first fault code displayed is the most recent.
Pushing the Totals button cycles through the fault codes. This mode will display the last 16
fault codes detected by the dispenser’s computer since the last RAM clear (not 16 per side
but 16 total for that computer).
In order to reset the dispenser after an Error or Hydraulic fault, the initial problem must be
corrected and power to the computer cycled or Option 99 is entered. Until these conditions
are satisfied the fault code will continue to be displayed at the end of the reset cycle.
FIGURE 3-3. FAULT CODE DISPLAY.
The fault code will have a format similar to that shown.
NNNNN.S
PF - CC.T
MAIN SALE DISPLAY
S = Side 1 or 2. This is the side on which the code was
detected.
T = Fault Code Status: 1 = Error 3 = Service
2 = Hydraulic 4 = Disable
NNNNN = Transaction Counter in the range of
00000 - 59999
CC = Fault Code number in the range of 00 - 99
F = Fault Source. This value identifies the fault source if the fault can be
linked to a particular hydraulic condition. The range is 0 - 7, "H" or "L".
The numeric values indicate positions (0 = none) while the letters
indicate blending feedstocks.
P = Product Source. This is the position that was selected at the time the
fault occurred. The range is 0 - 7, with 0 = no position selected.
TD00362-A
Summary of Contents for Dresser Vista 1 Series
Page 1: ...1 Vista Series Blending and Non Blending Remote Dispensers SERVICE ...
Page 4: ...Part No 920160 Rev A February 1997 ...
Page 10: ...viii Part No 920160 Rev A February 1997 ...
Page 12: ...2 Part No 920160 Rev A February 1997 ...
Page 22: ...12 Part No 920160 Rev A February 1997 ...
Page 38: ...28 Part No 920160 Rev A February 1997 ...
Page 62: ...52 Part No 920160 Rev A February 1997 ...
Page 76: ...66 Part No 920160 Rev A February 1997 FIGURE 7 8 NOZZLE BOOT ASSEMBLY LIFT TO START ...
Page 77: ...67 February 1997 Part No 920160 Rev A FIGURE 7 9 NOZZLE BOOT ASSEMBLY PUSH TO START ...
Page 83: ...73 February 1997 Part No 920160 Rev A APPENDIX A TROUBLESHOOTING FLOWCHARTS ...
Page 110: ...100 Part No 920160 Rev A February 1997 ...
Page 111: ...101 February 1997 Part No 920160 Rev A APPENDIX B SERVICE INFORMATION AND CONNECTOR PIN OUTS ...
Page 134: ...124 Part No 920160 Rev A February 1997 ...
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......