background image

Wattstopper

 

®

Multi-Way Wall Switch Convertible Occupancy Sensor
Détecteur de présence multivoies à interrupteur mural convertible
Sensor de Desocupación de pared configurable

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24261 – 09/16  rev. 1

Catalog Number • Numéro de Catalogue • Número de Catálogo: RH-250 

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

SPECIFICATIONS

Voltage .........................................................................120VAC, 60Hz
Load (Multi-Way)

Incandescent or fluorescent .......................................0-600 Watts
Fan motor ............................................................................ 1/6 hp

Time Delay Adjustment .................... 15 sec., 5 min., 15 min., 30 min.
Light Level Adjustment ..................................................10 fc to 150 fc
Environment ................................................................Indoor use only

Operating Temperature.......................... 32° to 131°F (0° to 55°C)
Humidity................................................ 95% RH, non-condensing

Tools Needed

Insulated Screwdriver
Wire Strippers

DESCRIPTION AND OPERATION

RH-250 Multi-way Wall Switch Convertible Occupancy Sensors are designed to replace standard single pole and multi-way (3-way, 4-way) 

switches. They are ideal for any room with multiple entries and any other indoor space where vacancy sensor-based controls with manual ON/

OFF capability are desirable.
Like standard switches, you can press the ON/OFF button to turn the light or fan (controlled load) ON and OFF. Unlike standard switches, the 

RH-250 automatically turns OFF the controlled load after the coverage area has been vacant for a period of time (Time Delay). If motion is 

detected within 30 seconds after it automatically turns OFF, the RH-250 automatically turns the load back ON.
While the sensor is factory preset as a Vacancy Sensor with manual ON operation, it can be adjusted to work as an occupancy sensor that turns 

the controlled load ON automatically upon detection of occupancy in the area.
The RH-250 can be wired with up to three additional RH-250s for multi-way Manual/Auto–ON/OFF of one or several loads (up to one load 

connected to each RH-250). It can also be wired to up to four RH-253 single pole momentary wall switches for multi-way Manual-ON/OFF 

Automatic-OFF control of one load.

Lighted Switch

To help you locate the RH-250 in a dark room, the amber LED illuminates the ON/OFF button while the controlled load is OFF. When the 

controlled load is ON, the LED is OFF.

Operating Modes

For multi-way operation of two or more RH-250s, we recommend that the Operating Mode be the same in all sensors related to the same load. 

This makes it easier to understand the multi-way control operation as well as trouble shooting. There are two operating modes to select from:

MODE 1

 Vacancy sensor (Manual-ON/OFF, Auto-OFF): The user must press the ON/OFF button to turn the load ON. The RH-250 keeps the 

load ON until no motion is detected by any of the related RH-250s for the time delay period. There is also a 30 second reset delay after the 

automatic shut-off. If motion is detected during this time, the sensor turns the load back ON automatically. After the 30 second reset delay has 

elapsed, the ON/OFF button must be pressed to turn ON the load.

MODE 2

 Occupancy sensor (Auto-ON/OFF with manual control and reset to auto after 5 minutes of vacancy): The load turns ON and OFF 

automatically based on occupancy detection. Once turned ON the RH-250 keeps the load ON until no motion is detected by any of the related 

RH-250s for the time delay period. If the load is turned OFF manually, automatic-ON is re-enabled when no motion is detected for 5 minutes. 

This prevents the load from being turned ON after it was deliberately turned OFF.

Time Delay

The time delay can be selected by the user during set up. It can be adjusted to any of these fixed values:15 seconds/5 minutes/15 minutes/30 

minutes. We recommend that the time delay be the same in all sensors related to the same load. This makes it easier to understand the multi-

way control operation as well as trouble shooting. For additional information on how to adjust it, please read the SENSOR ADJUSTMENT & 

PROGRAMMING section of this installation manual.

Light Level

When the operating mode is set for occupancy sensor, Mode 2 (Auto-ON) this feature prevents the sensor from automatically turning the lights 

ON if there is already enough light in the area. 
In a multi-way application, each sensor monitors the light level at it’s location. If any sensor related to the load detects motion AND the measured 

light level in that sensor’s area is lower than it’s Light Level setting, the load turns ON.
To adjust the light level, please read the SENSOR ADJUSTMENT & PROGRAMMING section of this installation manual.

Summary of Contents for RH-250

Page 1: ...rolled load is OFF When the controlled load is ON the LED is OFF Operating Modes For multi way operation of two or more RH 250s we recommend that the Operating Mode be the same in all sensors related to the same load This makes it easier to understand the multi way control operation as well as trouble shooting There are two operating modes to select from MODE 1 Vacancy sensor Manual ON OFF Auto OF...

Page 2: ...ores to the length indicated by the Strip Gauge in Fig 3 approx 1 2 inch 4 Wire the sensor Twist the existing wires together with the wire leads on the RH 250 sensor s as indicated in either step 4a or 4b Cap wires securely using wire nuts a Wiring two RH 250s in a 3 way configuration Connect the green or non insulated copper GROUND wire from the circuit to the green terminal on each RH 250 Connec...

Page 3: ... 2 inch to expose the mode button and adjustment trimpots For multi way operation the Operating Mode and the Time Delay adjustments should be the same in all sensors related to the same load Setting up the Operating Mode Select the operating mode by pressing the Mode button The amber LED behind the switch button blinks to indicate the selected mode The blink pattern repeats three times One blink i...

Page 4: ...ted the TEST mode The controlled load turns ON for 5 seconds each time the sensor detects motion After 5 seconds expire without motion detection the load turns OFF The controlled load turns ON automatically with the next motion detection and stays ON for 5 seconds 4 Repeat as necessary to ensure that the desired coverage areas are within detection range You can do this test for each RH 250 in your...

Page 5: ...inte manuellement l activation automatique est réactivée lorsqu aucun mouvement n est détecté pendant 5 minutes Cela permet d éviter que la charge ne s active automatiquement après avoir été volontairement désactivée Temporisation La temporisation peut être sélectionnée par l utilisateur pendant la configuration Elle peut être réglée sur l une des valeurs fixes suivantes 15 secondes 5 minutes 15 m...

Page 6: ...lage au fil blanc du RH 250 auxiliaire Raccordez le fil d alimentation de la boîte de circuits SOUS TENSION au fil noir du RS 250 auxiliaire et au fil VA ET VIENT 1 Raccordez le fil VA ET VIENT 1 depuis le fil noir du RH 250 auxiliaire au fil noir du RH 250 maître Raccordez le fil d alimentation de la lampe CHARGE au fil rouge du RH 250 maître Scellez le fil rouge sur le RH 250 auxiliaire Connecte...

Page 7: ... d inoccupation marche arrêt manuels extinction automatique Deux clignotements indiquent le mode 2 fonctionnement détecteur de présence marche arrêt automatique avec commande manuelle et réinitialisation à la commande automatique après 5 minutes d inoccupation Pour changer le mode appuyez une fois sur le bouton Mode pour régler l appareil au mode 1 ou appuyez deux fois sur le bouton Mode pour régl...

Page 8: ...tecteur repère un mouvement Après 5 secondes passées sans détection la charge s éteint La charge contrôlée s active automatiquement lors de la prochaine détection et reste active pendant 5 secondes 4 Répétez les étapes autant de fois que nécessaire de sorte que le champ de détection soit conforme à la zone de couverture recherchée Vous pouvez effectuer ce test pour chaque RH 250 de votre configura...

Page 9: ...be presionar el botón de ENCENDIDO APAGADO para encender la carga Uno o varios RH 250s controlando una misma carga la mantendrán encendida hasta que ninguno de ellos detecte movimiento por un periodo de tiempo denominado Retardo de Apagado configurable desde 15 segundos hasta 30 minutos Existe un periodo de 30 segundos inmediatamente después de que la carga se ha apagado automáticamente durante el...

Page 10: ...le blanco del otro RH 250 denominado como auxiliar El término maestro es utilizado acá únicamente para designar el sensor que esta conectado directamente a la carga controlada Conecte el cable de LINEA o FASE del circuito al cable negro del RH 250 auxiliar y al cable VIAJERO 1 Conecte el cable VIAJERO 1 proveniente del cable negro del RH 250 auxiliar al cable negro del RH 250 maestro Conecte el ca...

Page 11: ...deará una ó dos veces según sea Modo 1 ó Modo 2 El LED repetirá el patrón seleccionado tres veces Después de eso la unidad estará programada para operar en el modo seleccionado Ajuste del Retardo de Apagado Gire la perilla izquierda en dirección contraria a las manecillas del reloj para reducir el tiempo que permanecerá encendida la carga después de la última detección de movimiento valor mínimo 1...

Page 12: ...zca inmóvil La carga controlada se apagará después de 5 segundos si el sensor no detecta movimiento 3 Movilícese dentro del área de cobertura La carga controlada se encenderá por 5 minutos cada vez que el sensor detecte movimiento Después de transcurridos 5 segundos de no detección la carga se apagará La carga se encenderá automáticamente con la próxima detección y se mantendrá encendida por otros...

Reviews: