wattstopper CI-305 Installation Instructions Manual Download Page 9

DIP SWITCH SETTING

The CI-305 has 7 DIP switches under the cover. 

Time Delay: Switches 1, 2, 3

The sensor will hold the lights 

ON

 as long as 

occupancy is detected. The time delay countdown 

starts when no motion is detected. After no motion 

is detected for the length of the time delay, the 

sensor will turn the lights 

OFF

.

Walk Through Switch 4

Walk-through mode turns the lights 

OFF

 three 

minutes after the area is initially occupied, if no 

motion is detected after the first 30 seconds. If 

motion continues beyond the first 30 seconds, the 

selected time delay applies.

PIR Sensitivity: Switch 5

•  Minimum forces a reduced detection range for 

the PIR. 

•  Maximum 

forces the sensitivity to the maximum 

coverage area. This setting is constantly updated.

Service: Switch 6

To override all sensor functions, set DIP switch 6 to 

the 

ON

 position. The red LED will come on and stay 

on for the duration of the override. This bypasses 

the occupancy control functions of the sensor, but 

still allows the lights to be manually controlled with 

a light switch, if one is installed.

On Mode: Switch 7

The Manual 

ON

 function is facilitated by installing 

a momentary switch such as a Watt Stopper LVS-1 Momentary Toggle Switch, or 

RS2-3 Low Voltage Momentary Switch. This switch connects to the sensor’s Manual 

(Man.) Switch and +24V terminals as shown in the wiring diagram. Each time the 

switch is pressed, the load changes state. The sensor’s operation as related to the 

manually operated switch is determined by the setting for DIP switch 7.

DIP Switch Setting Chart

Switch#

5 minutes

10 minutes

15 minutes

20 minutes

25 minutes
30 minutes

30 seconds

1 2 3

Time Delay

Test Mode/20 min

5

 

Maximum 

PIR Sensitivity

 

Minimum 

6

 

Normal 

 

Service 

Service

7

 

Auto On 

 

Manual On 

On Mode

   = ON

     = OFF

= Factory Setting

4

Disabled 

Enabled 

Walk-Through

Visit our website for FAQs: www.wattstopper.com

Summary of Contents for CI-305

Page 1: ...ks Operating Temperature 32 to 131 F 0 to 55 C Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon DIP switch reset PIR Coverage...

Page 2: ...on 24V supplied by WattStopper Power Packs 24VAC or half wave rectified AC COVERAGE PATTERN The CI 305 sensors provide a 360 coverage pattern Two lens patterns are available The CI 305 provides up to...

Page 3: ...art to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI 305 in a closed office is off center Avoid pla...

Page 4: ...terminal on the sensor BLUE wire from power pack to Control Out terminal on sensor To add a MANUAL SWITCH such as the LVS 1 Momentary Toggle Switch or RS2 3 Low Voltage Momentary Switch to the above...

Page 5: ...2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches White Black Red Line Voltage Wire Color Legend Standard wiring...

Page 6: ...ge Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 305 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch set DIP switch 7 ON White Black Red Line...

Page 7: ...ver onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals o...

Page 8: ...the Time Delayis set for Test Mode using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Remain still The red LED should not flash The lights should turn off after 5 seconds If not see...

Page 9: ...sition The red LED will come on and stay on for the duration of the override This bypasses the occupancy control functions of the sensor but still allows the lights to be manually controlled with a li...

Page 10: ...on b Activating the manual switch while the load is ON turns the load OFF When the load is turned OFF manually as long as the sensor continues to detect occupancy the load stays OFF For the selected t...

Page 11: ...here is voltage replace the power pack 3 If LED is flashing rapidly 10Hz an overload condition exists When this is corrected the sensor will return to normal operation Check the blue wire connection I...

Page 12: ...Hz 225mA 20A ballast or incandescent 1HP 120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast ORDERING INFORMATION WARRANTY INFORMATION WattStopper warra...

Reviews: