wattstopper CI-305 Installation Instructions Manual Download Page 11

TROUBLESHOOTING

CAUTION

Turn power off at the circuit breaker 

 

before working with or near high voltage.

Lights do not turn ON with occupancy, and the following condition exists:

•  Red LED does not flash:

     1. Check that the circuit breaker has been turned back on.

     2. Check all sensor and power pack wire connections.

     3. Check for 24V input to the sensor.  

          - If 24V is present, replace the sensor. 

          - If 24V is not present, check that high voltage is present to power pack.  

             If it is, replace power pack.
     4. Make sure that PIR Sensitivity is set to minimum (DIP switch #5 set to 

on

).

     5. If it still does not flash, call 800.879.8585 for Technical Support.

•   LED flashes:

1.  Check all sensor and power pack wire connections.

2.   Check for 24VDC at the power pack’s blue wire connection to 

sensor while sensor is activated. If there is no voltage, replace 

the sensor. If there is voltage, replace the power pack

3.  If LED is flashing rapidly (~10Hz), an overload condition exists. When 

this is corrected, the sensor  will return to normal operation. Check 

the blue wire connection. If necessary, replace the power pack.

•  Line voltage switch connected as shown in wiring example.

1.  Make sure switch is set to 

ON

 position.

Lights do not turn OFF automatically:

1.   The sensor technology (PIR) may be experiencing activations 

from outside the controlled area or from some type of 

interference (see “Unwanted Sensor Activations” below).

2.  Check all sensor and power pack wire connections.

3.   Disconnect power pack’s blue wire: 

If the lights do not turn off, replace power pack. Reconnect blue wire. 

If the lights turn off, the problem may be in the sensor.

To check:

• 

Reconnect the blue wire.

 

• 

Turn sensitivity and time delay to minimum and allow the sensor to time out. 

 

• 

If the lights turn off, the sensor is working properly (see number 1, 

above, and “Sensor Adjustment” for readjustment of sensor).

Visit our website for FAQs: www.wattstopper.com

Summary of Contents for CI-305

Page 1: ...ks Operating Temperature 32 to 131 F 0 to 55 C Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon DIP switch reset PIR Coverage...

Page 2: ...on 24V supplied by WattStopper Power Packs 24VAC or half wave rectified AC COVERAGE PATTERN The CI 305 sensors provide a 360 coverage pattern Two lens patterns are available The CI 305 provides up to...

Page 3: ...art to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI 305 in a closed office is off center Avoid pla...

Page 4: ...terminal on the sensor BLUE wire from power pack to Control Out terminal on sensor To add a MANUAL SWITCH such as the LVS 1 Momentary Toggle Switch or RS2 3 Low Voltage Momentary Switch to the above...

Page 5: ...2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches White Black Red Line Voltage Wire Color Legend Standard wiring...

Page 6: ...ge Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 305 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch set DIP switch 7 ON White Black Red Line...

Page 7: ...ver onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals o...

Page 8: ...the Time Delayis set for Test Mode using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Remain still The red LED should not flash The lights should turn off after 5 seconds If not see...

Page 9: ...sition The red LED will come on and stay on for the duration of the override This bypasses the occupancy control functions of the sensor but still allows the lights to be manually controlled with a li...

Page 10: ...on b Activating the manual switch while the load is ON turns the load OFF When the load is turned OFF manually as long as the sensor continues to detect occupancy the load stays OFF For the selected t...

Page 11: ...here is voltage replace the power pack 3 If LED is flashing rapidly 10Hz an overload condition exists When this is corrected the sensor will return to normal operation Check the blue wire connection I...

Page 12: ...Hz 225mA 20A ballast or incandescent 1HP 120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast ORDERING INFORMATION WARRANTY INFORMATION WattStopper warra...

Reviews: