PLACEMENT GUIDELINES

Depending upon obstacles such as furniture or partitions, the area of coverage may 

be less or more than the sensing distances shown in the coverage pattern. This 

must be considered when planning the number of sensors and their placement. It 

is also recommended to place the sensor 4 to 6 feet away from air supply ducts as 

rapid air currents or the differences in temperatures may cause false activations.
Mount the sensor to the ceiling. The CI-305 sensors are designed for a ceiling 

height of about 8-10 feet. Mounting above or below this range will significantly 

affect the coverage patterns. Be aware that as you decrease the mounting height, 

you decrease the range and increase the sensitivity to smaller motions. Conversely, 

when you increase the height, you increase the range and decrease the sensitivity 

to smaller motions. At heights of more than 

12-14 feet, you may start to significantly 

reduce sensitivity. As a general rule, each 

occupant should be able to clearly view the 

sensor.
Often the best location to install a CI- 305 in 

a closed office is off-center. Avoid placing 

a sensor directly in line with an open door 

through which it has a clear view out, as the 

sensor may detect people walking by. 

Masking the PIR Lens:

 Opaque adhesive tape is supplied so that sections of the PIR 

lens can be masked. This restricts the sensor’s view and allows you to eliminate PIR 

coverage in unwanted areas such as hallways outside of the desired coverage area. 

Since masking removes bands of coverage, remember to take this into account 

when troubleshooting coverage problems. 

Open Office Area Coverage:

 To get complete 

coverage in an open office area, install 

multiple sensors so that there is an overlap 

with each adjacent sensor’s coverage area. 
For open office areas with partitions it is best 

to place sensors over intersection of four 

workstations.
For large areas of coverage use multiple 

sensors. 

CI-205

12'

18'

CI-205

36'

36'

Visit our website for FAQs: www.wattstopper.com

Summary of Contents for CI-305

Page 1: ...ks Operating Temperature 32 to 131 F 0 to 55 C Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon DIP switch reset PIR Coverage...

Page 2: ...on 24V supplied by WattStopper Power Packs 24VAC or half wave rectified AC COVERAGE PATTERN The CI 305 sensors provide a 360 coverage pattern Two lens patterns are available The CI 305 provides up to...

Page 3: ...art to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI 305 in a closed office is off center Avoid pla...

Page 4: ...terminal on the sensor BLUE wire from power pack to Control Out terminal on sensor To add a MANUAL SWITCH such as the LVS 1 Momentary Toggle Switch or RS2 3 Low Voltage Momentary Switch to the above...

Page 5: ...2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches White Black Red Line Voltage Wire Color Legend Standard wiring...

Page 6: ...ge Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 305 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch set DIP switch 7 ON White Black Red Line...

Page 7: ...ver onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals o...

Page 8: ...the Time Delayis set for Test Mode using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Remain still The red LED should not flash The lights should turn off after 5 seconds If not see...

Page 9: ...sition The red LED will come on and stay on for the duration of the override This bypasses the occupancy control functions of the sensor but still allows the lights to be manually controlled with a li...

Page 10: ...on b Activating the manual switch while the load is ON turns the load OFF When the load is turned OFF manually as long as the sensor continues to detect occupancy the load stays OFF For the selected t...

Page 11: ...here is voltage replace the power pack 3 If LED is flashing rapidly 10Hz an overload condition exists When this is corrected the sensor will return to normal operation Check the blue wire connection I...

Page 12: ...Hz 225mA 20A ballast or incandescent 1HP 120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast ORDERING INFORMATION WARRANTY INFORMATION WattStopper warra...

Reviews: