SENSOR ADJUSTMENT
This unit is pre-set for basic operation as described
in this guide. Adjustment is optional.
The sensors are factory preset to allow for quick installation in most applications.
Verification of proper wiring or coverage, or customizing the sensor’s settings can
be done using the following procedures. To make adjustments, open the Front
Cover by pulling on the
cover tab.
There is a 30 second
warm-up period when
power is first applied.
Before making
adjustments, make
sure the office furniture
is installed, lighting
circuits are turned on,
and the HVAC systems
are in the overridden/on
position. VAV systems
should be set to their
highest airflow. Set the
DIP switches to the
desired settings. See “DIP Switch Setting”.
To Test Occupancy Sensors
1. Ensure the Time Delayis set for
Test Mode*
using the “Test Mode/20 minutes”
setting. (DIP switches 1 ,2, & 3 are
OFF
).
2. Remain still. The red LED should not flash. The lights should turn off after
5 seconds. (If not, see “Troubleshooting.”)
3. Move about the coverage area. The lights should come on.
When testing and adjustment is complete, reset DIP Switches to the desired
settings, and replace the cover on the sensor.
* Test Mode
is a temporary state that starts when you first set the sensor’s DIP
switches for the “Test Mode/20 minutes” (switches 1, 2, 3
OFF
). If you need to
invoke the
Test Mode
and the DIP switches are already set for Test Mode/20
minutes, toggle DIP switch 1
ON
then back to the
OFF
position. This provides a
10 minute test period. During the test period, the Time Delay is only 5 seconds.
Keyhole slots
(for mounting to
4" octagonal box)
Double gang
mudring
mounting holes
DIP
switches
PIR lens
ON
1
2
3
4
5
6
7
ECE
PIR Activity
LED (Red)
Call 800.879.8585 for Technical Support