wattstopper CI-305 Installation Instructions Manual Download Page 2

UNIT DESCRIPTION

The WattStopper CI-305 360° passive infrared (PIR) occupancy sensors turn lighting 

systems on and off based on occupancy. 
The sensors can be configured to turn lighting on, and hold it on as long as the 

sensor detects occupancy. After no movement is detected for a user specified time 

(30 seconds to 30 minutes) the lights are switched off. A “walk-through” mode can 

turn lights off after only 3 minutes, if no activity is detected after 30 seconds of an 

occupancy detection.
The CI-305 operates on 24V supplied by WattStopper Power Packs, 24VAC or half 

wave rectified AC.

COVERAGE PATTERN

The CI-305 sensors provide a 360° coverage pattern. Two lens patterns are 

available. The CI-305 provides up to 1200 square feet of coverage and the CI-305-1 

provides up to 500 square feet of coverage. The coverage shown represents walking 

motion at a mounting height of 8 feet. For building spaces with lower levels of 

activity or with obstacles and barriers, coverage size may decrease.

Call 800.879.8585 for Technical Support

24 ft

7.3m

CI-305-1 Coverage Pattern (high density, reduced range lens)

44 ft

13.4m

CI-305 Coverage Pattern (standard lens)

Drawings not to scale.

Side View

Side View

Top View @ 8ft

Top View @ 8ft

Summary of Contents for CI-305

Page 1: ...ks Operating Temperature 32 to 131 F 0 to 55 C Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon DIP switch reset PIR Coverage...

Page 2: ...on 24V supplied by WattStopper Power Packs 24VAC or half wave rectified AC COVERAGE PATTERN The CI 305 sensors provide a 360 coverage pattern Two lens patterns are available The CI 305 provides up to...

Page 3: ...art to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI 305 in a closed office is off center Avoid pla...

Page 4: ...terminal on the sensor BLUE wire from power pack to Control Out terminal on sensor To add a MANUAL SWITCH such as the LVS 1 Momentary Toggle Switch or RS2 3 Low Voltage Momentary Switch to the above...

Page 5: ...2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches White Black Red Line Voltage Wire Color Legend Standard wiring...

Page 6: ...ge Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 305 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch set DIP switch 7 ON White Black Red Line...

Page 7: ...ver onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals o...

Page 8: ...the Time Delayis set for Test Mode using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Remain still The red LED should not flash The lights should turn off after 5 seconds If not see...

Page 9: ...sition The red LED will come on and stay on for the duration of the override This bypasses the occupancy control functions of the sensor but still allows the lights to be manually controlled with a li...

Page 10: ...on b Activating the manual switch while the load is ON turns the load OFF When the load is turned OFF manually as long as the sensor continues to detect occupancy the load stays OFF For the selected t...

Page 11: ...here is voltage replace the power pack 3 If LED is flashing rapidly 10Hz an overload condition exists When this is corrected the sensor will return to normal operation Check the blue wire connection I...

Page 12: ...Hz 225mA 20A ballast or incandescent 1HP 120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast ORDERING INFORMATION WARRANTY INFORMATION WattStopper warra...

Reviews: