WIRING DIRECTIONS
CAUTION
Turn power off at the circuit breaker before
installing power packs or sensors.
Each WattStopper BZ series power pack
can supply power for 14 CI-305 sensors.
When using more sensors than this,
multiple power packs are required.
Refer to the wiring diagram on the next
page for the following procedures:
Connect the
low voltage
:
• RED wire (+24VDC) from power pack to
the +
24V
terminal on the sensor.
• BLACK wire (Return) from power pack
to
Common
terminal on the sensor.
• BLUE wire from power pack to
Control
Out
terminal on sensor.
To add a MANUAL SWITCH
such as the
LVS-1 Momentary Toggle Switch, or RS2-3 Low Voltage Momentary Switch to the
above applications–connect:
• Wire from one side of switch to +24 terminal on sensor.
• Wire from other side of switch to Man Switch terminal on sensor.
Call 800.879.8585 for Technical Support
CI-305
Passive Infrared
Occupancy Sensor
U.S.Patents:
5,640,113
Patent Pending
+24VDC/VAC
Connect to Watt Stopper
Class 2 Power Packs
For Indoor Use Only
03083r2
www.wattstopper.com
800.879.8585
Control Out.
Man. Switch
+24V
Common
LISTED
88T9
Appliance
Control
v3
Wiring
terminals