wattstopper CI-305 Installation Instructions Manual Download Page 4

WIRING DIRECTIONS

CAUTION

Turn power off at the circuit breaker before 

installing power packs or sensors.

Each WattStopper BZ series power pack 

can supply power for 14 CI-305 sensors. 

When using more sensors than this, 

multiple power packs are required.
Refer to the wiring diagram on the next 

page for the following procedures:

Connect the 

low voltage

•  RED wire (+24VDC) from power pack to  

  the +

24V

 terminal on the sensor.

•  BLACK wire (Return) from power pack  

 to 

Common

 terminal on the sensor.

•   BLUE wire from power pack to 

Control 

Out

 terminal on sensor.

To add a MANUAL SWITCH

 such as the 

LVS-1 Momentary Toggle Switch, or RS2-3 Low Voltage Momentary Switch to the 

above applications–connect:

•  Wire from one side of switch to +24 terminal on sensor.
•  Wire from other side of switch to Man Switch terminal on sensor.

Call 800.879.8585 for Technical Support

CI-305

Passive Infrared

Occupancy Sensor

U.S.Patents:

5,640,113

Patent Pending

+24VDC/VAC

Connect to Watt Stopper 

Class 2 Power Packs

For Indoor Use Only

03083r2

www.wattstopper.com

800.879.8585

Control Out.

Man. Switch

+24V

Common

LISTED

88T9

Appliance

Control

v3

Wiring 

terminals

Summary of Contents for CI-305

Page 1: ...ks Operating Temperature 32 to 131 F 0 to 55 C Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon DIP switch reset PIR Coverage...

Page 2: ...on 24V supplied by WattStopper Power Packs 24VAC or half wave rectified AC COVERAGE PATTERN The CI 305 sensors provide a 360 coverage pattern Two lens patterns are available The CI 305 provides up to...

Page 3: ...art to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI 305 in a closed office is off center Avoid pla...

Page 4: ...terminal on the sensor BLUE wire from power pack to Control Out terminal on sensor To add a MANUAL SWITCH such as the LVS 1 Momentary Toggle Switch or RS2 3 Low Voltage Momentary Switch to the above...

Page 5: ...2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches White Black Red Line Voltage Wire Color Legend Standard wiring...

Page 6: ...ge Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 305 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch set DIP switch 7 ON White Black Red Line...

Page 7: ...ver onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals o...

Page 8: ...the Time Delayis set for Test Mode using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Remain still The red LED should not flash The lights should turn off after 5 seconds If not see...

Page 9: ...sition The red LED will come on and stay on for the duration of the override This bypasses the occupancy control functions of the sensor but still allows the lights to be manually controlled with a li...

Page 10: ...on b Activating the manual switch while the load is ON turns the load OFF When the load is turned OFF manually as long as the sensor continues to detect occupancy the load stays OFF For the selected t...

Page 11: ...here is voltage replace the power pack 3 If LED is flashing rapidly 10Hz an overload condition exists When this is corrected the sensor will return to normal operation Check the blue wire connection I...

Page 12: ...Hz 225mA 20A ballast or incandescent 1HP 120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast ORDERING INFORMATION WARRANTY INFORMATION WattStopper warra...