DO NOT exceed the rated flow rate capacity of the system. Flow controllers are available from
Lync to ensure system's rated flow is not exceeded. Follow all product safety labeling. DO NOT
let the system freeze. System damage may result. Install the system on a flat, and level surface.
The quality of the water to be treated must meet the feed water guidelines within this manual.
Failure to ensure proper pretreatment will result in inadequate disinfection
1.2.
Specifications
WQ-AS Skid
WQAS-050-D
WQAS-100-D
Peak flow rate
50 gpm
100 gpm
Number of Lync UV systems (LD050AGAA)
1
2
Number of Lync Cartridge Filter systems
1
Number of AquaSolve systems
1
2
Inlet/Outlet
2”
SCH80 PVC Flange
Operating pressure
28 psi to 125 psi
Max ambient temperature/humidity
122
o
F / 95 % relative humidity (non-condensing)
Operating temperature
40
o
F - 100
o
F (5
o
C - 38
o
C)
Max hardness
30 Grains (513 mg/L as CaCO
3
)
Max free chlorine
2 ppm
Max iron
0.3 ppm
Max manganese
0.05 ppm
Max copper
1.3 ppm
Max silica
20 ppm
Max TDS
1500 ppm
pH
6.5
– 8.5
Total phosphate
3 ppm or less
Oil and H
2
S
Not allowed
Dimension W x D x H (inches)
78 x 24 x 82
132 x 24 x 82
Shipping weight (lbs)
700
1100
Lync UV
Flow rate per UV system @ 30mJ (95%UVT @EOL)
50 gpm
UV Transmittance
95 % UVT
Standard NPT inlet / outlet ports
1.5"NPT-M / 1"NPT-F Combo Ports
Chamber material
316L SS
Controller mounting
On chamber bracket
Input voltage
120 to 240VAC, 50/60 Hz
Max nominal input power for each UV system (Watts)
118