Lync WQ-AS 

SECTION 3: OPERATION 

L- OMM-007_A

   

 

  

 

5/6/2022

 

Technical Support  •  (800) 433-5654  •  Mon-Fri, 8 am - 5 pm EST 

 27 

 of 

42

 

3.7.9.  Measured UV Level, Absolute 

Input Register Address: 0x0476 : 0x0477 

These registers display the measured UV intensity level reported by the external UV sensor. 

The value is reported in units of 0.01W/m2 

The value 4294967295 (0xFFFFFFFF) is reserved to indicate that the UV level has overflowed 
the measurement range of the sensor device. 

 

 

 

 

Summary of Contents for Lync WQ-AS

Page 1: ...The information contained in this manual is subject to change without notice from Lync a division of Watts Water Technologies Inc Lync makes no warranty of any kind with respect to this material inclu...

Page 2: ...3 6 5 Set Up Screen 18 3 6 6 Bypassing Alarms Alarm Relay Output 18 3 6 7 Bypassing Alarms Audible Alarms 19 3 6 8 Lamp and Sleeve Replacement Screen 19 3 7 Modbus Communication 20 3 7 1 Serial Commun...

Page 3: ...nc WQ AS Table of Contents L OMM 007_A 5 6 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 3 of 42 6 2 Routine Cartridge Replacement 40 6 3 Lync UV Maintenance 40 6 4 Disinfection Procedure...

Page 4: ...The LM8414TM COM is certified through WQA against NSF ANSI CAN Standard 61 CSAB483 1 and to NSF ANSI 372 for Lead Free compliance Lync cartridge filtration system includes filter housing LCH 150 and a...

Page 5: ...V C emitter UV lamp Unintended use of the appliance or damage to the housing may result in the escape of dangerous UV C radiation UV C radiation may even in little doses cause harm to the eyes and ski...

Page 6: ...D050AGAA 1 2 Number of Lync Cartridge Filter systems 1 Number of AquaSolve systems 1 2 Inlet Outlet 2 SCH80 PVC Flange Operating pressure 28 psi to 125 psi Max ambient temperature humidity 122 oF 95 r...

Page 7: ...ay manual over ride Yes Lync Cartridge Filter Lync Cartridge Filter size 5 micron Material filter body cartridge end caps Glass reinforced PP Brass reinforced gauge port 1 4 FNPT Material swing bolts...

Page 8: ...should be performed to determine proper application where hardness levels exceed 30 grains per gallon Just as with conventional water softening media AquaSolve media needs to be protected from excess...

Page 9: ...nc WQ AS COMPONENTS L OMM 007_A 5 6 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 9 of 42 2 Lync WQ AS Components 2 1 WQ AS Skid Components WQAS 050 D WQAS 100 D Figure 2 1 General WQ AS C...

Page 10: ...et Kit X 1 1 Quartz Sleeve O Ring X 1 2 3 2 Installation Location Lync WQ AS is a complete system with factory pre assembled plumbing and wiring to minimize installation time and labor Components are...

Page 11: ...er s by closing inlet and outlet valves 5 If no isolation valve exists at system installation location it is recommended to install an isolation valve located within 10 feet of the system 6 After fina...

Page 12: ...ounded in accordance with all local codes and ordinances NOTE The system MUST be plugged into an uninterrupted power supply that matches the rated power requirement of the system In European installat...

Page 13: ...e startup Verify that the outlet isolation valve after the skid and the inlet and outlet valves of the UV system s are open Slowly partially open the supply water valve to the skid Slowly open the inl...

Page 14: ...ebed due date on product label located on the front of each tank as a reminder to replace AquaSolve media every 3 years The system is now ready for service 3 6 Lync UV Controller The Lync UV controlle...

Page 15: ...ally appear This is the screen that the system will display during normal operation From the Home Screen four sub screens can be accessed by touching the icons Home Screen Sub Screens 1 History Screen...

Page 16: ...en the system advances to the Lamp Warm Up Screen If an abnormal condition exists a variety of alarms can be displayed 3 6 4 Possible Alarms Upon start up of the system if the UV sensor is not found t...

Page 17: ...screen This graphic shows the lamp to be in a dimmed condition to reduce water temperature and conserve energy If the system detects low UV intensity a yellow warning will appear If the UV intensity...

Page 18: ...connections to the controller Clean or replace sensor if needed 3 6 5 Set Up Screen The Set Up Screen can be accessed by pressing the gear icon on the Home Screen This allows the user to select a lan...

Page 19: ...relay is not bypassed 3 6 7 Bypassing Alarms Audible Alarms Touching the speaker icon will bring up a confirmation screen Touch Yes to mute the audible alarm for 24 hours and return to the Set Up Scre...

Page 20: ...on Remote communication of the Lync UV control system utilizes Modbus over a RS 485 protocol Connect the RJ45 cable into CAT 5 ethernet connection port at the bottom of Lync UV controller see section...

Page 21: ...Group 0x0374 LampType Lamp Type LMS 0x0375 LampRatedOpTime Lamp Rated Operating Time LMS 0x0470 ControllerOpTimeH Controller Cumulative Operating Time high word CLOD 0x0471 ControllerOpTimeL Controlle...

Page 22: ...mp Type Input Register Address 0x0374 This register identifies the specific model of UV lamp that has been attached to the controller This value applies to the last lamp for which the lamp tag was suc...

Page 23: ...3 7 5 Lamp Rated Operating Time Input Register Address 0x0375 This register displays the rated operating time of the UV lamp in hours This value applies to the last lamp for which the lamp tag was suc...

Page 24: ...upport 800 433 5654 Mon Fri 8 am 5 pm EST 24 of 42 3 7 6 Controller Operating Time Input Register Address 0x0470 0x0471 These registers display the cumulative operating time of the controller The Cont...

Page 25: ...t Register Address 0x0472 0x0473 These registers display the cumulative time that the lamp has been operating The value is specified in units of 15 minute intervals This value applies to the last lamp...

Page 26: ...er Address 0x0475 This register displays the number of days of operation that remain for the lamp before it will have been operated for its rated maximum lifetime or longer This value applies to the l...

Page 27: ...red UV Level Absolute Input Register Address 0x0476 0x0477 These registers display the measured UV intensity level reported by the external UV sensor The value is reported in units of 0 01W m2 The val...

Page 28: ...L OMM 007_A 5 6 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 28 of 42 3 7 10 Controller Status Information Group 0 Input Register Address 0x0479 This register displays various runtime ope...

Page 29: ...Lync WQ AS SECTION 3 OPERATION L OMM 007_A 5 6 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 29 of 42...

Page 30: ...Lync WQ AS SECTION 3 OPERATION L OMM 007_A 5 6 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 30 of 42...

Page 31: ...L OMM 007_A 5 6 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 31 of 42 3 7 11 Controller Status Information Group 1 Input Register Address 0x047A This register displays various runtime ope...

Page 32: ...Lync WQ AS SECTION 3 OPERATION L OMM 007_A 5 6 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 32 of 42...

Page 33: ...eed water meets the feed water requirements within this manual UV sensor fouled or defective Clean or replace UV sensor Low power to lamp Replace controller Lamp intensity does not increase with water...

Page 34: ...ure 5 1 WQ AS Skid Parts Item Description Part 1 Lync Filter Cartridge LCB 150 P5 68100632 2 Lync Filter Housing LCH 150 68110217 3 Lync UV 50 GPM LD050AGAA 68110226 4 1 5 x 24 SS Flex Connector 68110...

Page 35: ...e Cross Section Item Description Part 1 Stainless Steel Tank Head 68106656 2 Upper Basket Assembly 68101233 3 1 5 Riser 68103367 4 Bottom Distributor Assembly 68101235 5 14 X 65 AquaSolve Tank Body 68...

Page 36: ...Parts Item Description Part 1 Pressure relief assembly includes cap spring and stem 68100621 2 Lid with brass reinforced gauge port 68100616 3 O ring for lid closure EPDM 68100619 4 Adapter 2 PVC 6810...

Page 37: ...re 5 4 Lync UV Parts Item Description Part 1 Flow Switch with Cable for All Systems 68108175 2 UV Sensor Accessory Kit with Cable for Controller 68108148 3 Plug for UV Sensor Port when Sensor is Not U...

Page 38: ...t below for pressure drop data 6 1 Replacing AquaSolve Media 1 Shut off the primary feed supply going to the WQ AS skid 2 Close the inlet valve to the AquaSolve s and the inlet valve to Lync Cartridge...

Page 39: ...need to take it out in small bites If you let the whole pipe hose fill with media it will plug up You need to let slugs of water flush out the pipe as you go Figure 6 1 Replacing LM8414TM COM Media 11...

Page 40: ...to engage locking tabs Lubricating O rings if necessary 29 Check lid O ring to ensure it is properly seated Lubricate if necessary 30 Replace lid 31 Replace eyebolts and tighten Hand tight is sufficie...

Page 41: ...leeve from reactor chamber E 9 Fully insert a new quartz sleeve into the reactor chamber and install the O ring over the quartz sleeve Press the O ring down over the quartz sleeve until it is seated i...

Page 42: ...lter line 2 Depressurize the cartridge filter and unscrew the housing 3 Install a new filter cartridge and pour 1 cup of 6 bleach into the housing 4 Reinstall the filter housing and open up the filter...

Reviews: