If hot water is used during disinfection procedure, please use UV Sensor Port Plug #
T7402210 and Flow Sensor Port Plug # T7401003.
DO NOT unplug the system.
1. Shut off the inlet and outlet isolation valves on the cartridge filter line.
2. Depressurize the cartridge filter and unscrew the housing.
3. Install a new filter cartridge and pour 1 cup of 6% bleach into the housing.
4. Reinstall the filter housing and open up the filter isolation valves.
5. Flush 2 reactor chamber volumes of water through the UV system(s) then stop and let the
solution remain in the UV system(s) for 30 minutes.
6. After 30 minutes, flow enough water through the system to flush all of the residual chlorine
from the system. During this time
DO NOT
exceed the rated flow rate of the UV system.