Lync WQ-AS
SECTION 5: MAINTENANCE
L- OMM-007_A
•
5/6/2022
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
40
of
42
19. Put the tank in service.
Alternative Method for Replacing Media
Follow steps 1
– 6 then:
20. Remove center distributor tube and lower basket and siphon all water from tank
21. Lay tank down on its side and tip upside down while using hose to flush media out
22. When all the old media is removed, stand tank back up and install in original position. Fill
the tank so that it is about half full with water.
Then continue with steps 12
– 19.
6.2.
Routine Cartridge Replacement
The Lync filter cartridge needs to be cleaned or replaced with a new cartridge at the maximum
of 15 psi differential pressure.
23. Close inlet valve.
24. Close outlet valve.
25. Press pressure relief button to relieve pressure.
26. Remove lid after pressure has been relieved.
27. Rotate cartridge counterclockwise and pull upward to remove the cartridge.
28. Install new (or cleaned) cartridge. Push downward and rotate clockwise to engage locking
tabs. Lubricating O-rings if necessary.
29. Check lid O-ring to ensure it is properly seated . Lubricate if necessary .
30. Replace lid.
31. Replace eyebolts and tighten. (Hand tight is sufficient.)
32. Open outlet pipe completely.
33. Open inlet pipe slowly to check for leaks.
34. Vent filter to dispel air by depressing pressure relief button. Be careful when relieving
pressure or dispelling air if high temperature water is being filtered.
NOTE:
If leaks occur, close the inlet and outlet pipes and follow procedures previously
described under WARNING in Section 3.3: Plumbing and UV Connections.
6.3.
Lync UV Maintenance
UV Lamps have a
1 year (9000 Hour) life span
under normal operating conditions. Quartz
sleeves should be cleaned with vinegar, citric acid, or a lime scale removing chemical annually
and replaced no less than once every 3 years. If the quartz sleeve cannot be cleaned, or if it is
discolored, is must be replaced. Pre filters should be maintained according to the
manufacturer’s instructions to ensure feed water requirements within this manual are met.
Lamp and Quartz Sleeve Replacement Procedure:
WARNING!
If any water comes in contact with any electrical components, dry the components