background image

2

Installation Guidelines

NOTICE

 

The flange gasket bolts for the gate valves should be 

retightened during installation as the bolts may have loosened 

due to storage and shipping.

1.  Consult local codes for specific installation requirements and 

restrictions applicable to your area. At least 20 psi (133 kPa) is 

recommended for system supply pressure.

2.  Install the valves only in the orientation or flow direction shown.  

These instructions apply only to Series LF860-FS and LF866-FS, 

sizes 2½" to 10". 

3.  Install the valve assembly where it is accessible for periodic 

testing and maintenance. Clearances shown in the installation 

views apply to interior, and pit or vault installations and are  

only recommendations. (See Figures 1 and 2.) These mini-

mums do not apply to removable protective enclosures. Refer 

to local codes for actual requirements of the area.

4.  Before installing the valve into the line, flush the supply line of 

all foreign materials. Failure to flush the supply line can cause 

the check valves to become fouled and require disassembly 

and cleaning.

5.  Do not lift the assembly by connecting to the gate valve hand-

wheels or stems. 

6.  After installation, slowly fill the assembly with water and bleed 

air from the body using test cocks No. 2, No. 3, and No. 4. 

Test the valve assembly to ensure correct operation.

NOTICE

 

All assemblies are tested at the factory for proper operation and 

leakage. If the valve does not pass the field test, it is most likely 

due to a fouled check valve. This is not covered by the factory 

warranty. The valve cover(s) must be removed and the check 

seats inspected and cleaned. Any damage or improper operation 

caused by pipeline debris or improper installation/start-up is not 

included in the factory warranty. In case of a possible warranty 

claim, contact the local supplier or FEBCO representative. Do not 

remove the valve assembly from the pipeline.

7.  Protect the assembly from freezing and excessive pressure 

increases. Pressure increases can be caused by thermal 

expansion or water hammer. These excessive pressure  

situations must be eliminated to protect the valve and system 

from possible damage.

NOTICE

 

The gap drain is not designed to catch the maximum discharge 

possible from the relief valve. The installation of a FEBCO

®

 air 

gap with the drain line terminating above a floor drain handles 

any normal discharge or nuisance spitting through the relief valve. 

However, floor drain size may need to be designed to prevent 

water damage caused by a complete failure condition. Do not 

reduce the size of the drain line from the air gap fitting.

When installing an air gap, attach the air gap brackets directly 

onto the flood sensor.

Figure 1

Figure 2

12" min. 

Refer to Local 

Codes

FLOW

Horizontal Installation

(Shown with strainer)

Horizontal Installation

(Top view, shown with strainer)

18" min. 

Refer to Local Codes

12" min. 

Refer to Local Codes

6" min.  

Refer to Local 

Codes

Typical Installation

Summary of Contents for LF860-FS Large Series

Page 1: ...ilure to do so may result in a malfunctioning assembly IS F 860RP RPDA FS Installation Maintenance and Repair Manual Series LF860 FS Large and LF866 FS Reduced Pressure Zone Assemblies Reduced Pressur...

Page 2: ...tory for proper operation and leakage If the valve does not pass the field test it is most likely due to a fouled check valve This is not covered by the factory warranty The valve cover s must be remo...

Page 3: ...f valve of a new installation linked to a BMS controller not included 88009415 FP RFK FBF BMS CFS 21 2 10 BMS Sensor Retrofit Connection Kit Series LF860 Large LF866 LF880V LF886V Sizes 2 to 10 Includ...

Page 4: ...if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any oth...

Page 5: ...donner lieu un dysfonctionnement du syst me IS F 860RP RPDA FS Manuel d installation d entretien et de r paration S rie LF860 FS Large et LF866 FS Ensembles pour zones pression r duite Dispositifs de...

Page 6: ...ne passe pas le test sur le terrain cela est tr s probablement d un clapet antiretour encrass Ceci n est pas couvert par la garantie de l usine Les couvercles de vanne doivent tre retir s et les si g...

Page 7: ...ation avec contr leur BMS non inclus 88009415 FP RFK FBF BMS CFS 21 2 10 Trousse de connexion de mise niveau de capteur BMS S rie LF860 Large LF866 LF880V LF886V Tailles 2 po 10 po 6 3 cm 24 4 cm Comp...

Page 8: ...s correctement autres co ts aff rents aux frais de main d uvre de retards de vandalisme de n gligence d engorgement caus s par des corps trangers de dommages caus s par des propri t s de l eau d favor...

Page 9: ...no hacerlo puede resultar en un ensamble defectuoso IS F 860RP RPDA FS Manual de instalaci n mantenimiento y reparaci n Serie LF860 FS Large y LF866 FS V lvulas antirretorno de principio de presi n re...

Page 10: ...recta y la ausencia de fugas Si la v lvula no pasa la prueba de campo lo m s probable es que se deba a una v lvula de retenci n contaminada Esto no est cubierto por la garant a de f brica Se deben ret...

Page 11: ...de detecci n de inundaciones en la v lvula de alivio de una nueva instalaci n conectada a un controlador BMS no incluido 88009415 FP RFK FBF BMS CFS 21 2 10 Kit de conexi n de retroadaptaci n del sens...

Page 12: ...rrectamente otros costos resultantes de cargos laborales retrasos vandalismo negligencia contaminaci n causada por materiales extra os da os por condiciones adversas del agua productos qu micos o cual...

Reviews: