Closing Shutoff Valves Prior to Maintenance
1. Slowly rotate shutoff valve #2 handle (C) clockwise to the
closed position. Flag perpendicular to flow (A).
2. Slowly rotate shutoff valve #1 handle (B) clockwise to the
closed position. Flag perpendicular to flow (A).
NOTICE
When yellow/orange position indicator flags are parallel with the flow of water
the shutoff valves are in the open position. Before doing any maintenance be
sure the yellow or orange flow indicators (flags) are perpendicular to the flow
of water valve body indicating shutoff valves are in the closed position (A).
FLOW
FLOW
B
A
A
C
A
Opening Test Cocks and Bleeding All Pressure
from the Line Before Maintenance
NOTE: valve is still under pressure. When opening test cocks,
water will be released. Take precautions to ensure discharging
water does not damage the surrounding area/equipment or
create an unsafe condition.
1.
DO NOT OPEN
Main test cock number 1, as it is still
subject to line pressure.
2. Using the Deringer
TM
test cock wrench or a small
adjustable wrench open (A) main test cock number 4.
(Test cock is open when wrench flats are parallel to water
flow through test cock).
3. Deringer 50/50X only: using a #2 flathead screwdriver open
bypass test cock number 2. (Test cock is open when screw-
driver slot is parallel to water flow through test cock (B)).
4. Using the Deringer test cock wrench or a small adjustable
wrench open main test cock number 3.
5. Deringer 50/50X only: using a #2 flathead screwdriver open
bypass test cock number 1.
6. Using the Deringer test cock
wrench or a small adjustable
wrench open main test
cock number 2.
FLOW
B
B
A
A
Shut-off Valve (SOV)
Number 1
Shut-off Valve (SOV)
Number 2
Bypass Test Cock
Main Test Cock
Closed
Open
Closed
Open