Start Sequence
Figure 3-2b: BMK1500
– 6000 Air/Fuel Valve in Purge Position
5. Next, the Blower Proof and Blocked Inlet switches close (Figure 3-4a and 3-4b). On the
Ignition Sequence screen, the
Purging
indicator turns grey while purging is underway
(Figure 3-3) and
Purge Timer
displays the purge cycle
’s elapsed time in seconds.
Figure 3-3: Ignition Sequence Screen
– Purging
TO BLOWER
STEPPER
MOTOR
AIR IN
PURGE
VALVE POSITION
DIAL AT 100%
BLOWER PROOF SWITCH
BLOCKED INLET SWITCH