Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7
– BOILER SEQUENCING TECHNOLOGY
OMM-
0137_E • GF-211 • 12/13/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
100
of
153
OPTION 6
Instructions: Remote Setpoint, Direct Wired Header Temp Sensor, Modbus Setpoint
Drive
NOTES:
•
Polarity must be observed for the RS485 connections. The ground for the shield is at
the “SHLD” terminal in the I/O the Board.
•
The
Outdoor Temp Sensor
must be mounted on the North side of the building where
an average outside air temperature is expected. The sensor must be shielded from
direct sunlight as well as impingement by the elements. The
Outdoor Temp Sensor
may be wired up to 200 feet (61m) from the boiler.
•
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
Step 3
– OPTION 6 CONFIGURATION
On All Boiler:
1. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Configuration
:
•
Set the
Unit Mode
parameter to
BST Client
.
2. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Communication
:
•
Set the
Unit Address
parameter to the communication address of the unit.
On the BST Manager
only
:
1. Go to
Main Menu
→
Advanced Setup
→
BST Cascade
, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Unit Mode
BST Manager
Hdr Temp Sensor
Header Temp
Application
Configuration
Application
Space Heating
SH Operating Mode
Rmt Setpt Netwrk
Cascade
Communication
Min Address
The
minimum
unit address in the cascade
Max Address
The
maximum
unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.