Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7
– BOILER SEQUENCING TECHNOLOGY
OMM-
0137_E • GF-211 • 12/13/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
101
of
153
7.3.7 Option 7 Remote Setpoint: Modbus Header Temp Sensor & 4-
20ma Setpoint Drive
OPTION 7
Instructions: Remote Setpoint, Modbus Header Temp Sensor & 4-20ma Setpoint
Drive
NOTE:
Both
Header Temp Sensor
and
4-20ma Direct Drive
must be wired. See the
Edge
Controller Manual
(OMM-0139, GF-213) for more information.
Step 1:
MODBUS
HEADER TEMP SENSOR WIRING
– ANY BOILER
1. Connect the
Modbus Transmitter
terminal
Pin B
to the I/O board strip
J3
, terminal
13
(
BST RS485+)
and
Pin A
to terminal
15
(
BST RS485
–
) on any of the Boiler units using
shielded pair 18 - 22 AWG cable.
2. Connect the shield to any
Shield
terminal, such as terminal
3
or
8
on strip
J3
.
3. Connect the
Header Temp Sensor
to pins
2
and
3
of the
Modbus Transmitter
units using
shielded pair 18 - 22 AWG cable.
3. Install a jumper wire between pins
1
and
2
of the
Modbus Transmitter
.
NOTES:
•
Polarity must be observed for the RS485 connections.
•
Ground the shield to any
Shield
terminal on the I/O board, such as terminal
3
.
•
The
Header Temp Sensor
must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant’s supply water header.
•
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
Step 2: DIRECT WIRED 0-20mA OR 4-20mA WIRING
– BST MANAGER
1. Connect the
4-20mA
or
0-20mA
terminals from the Direct Drive source to the I/O board
strip
J3
, terminal 6
(
Remote Analog In +
) and terminal
7
(
Remote Analog In
–
) on the BST
Manager.
2. Connect the shield to any
Shield
terminal on the I/O board, such as terminal
3
or
8
.
NOTES:
•
Shielded pair 18 - 22 AWG cable is recommended for this connection. Polarity must be
observed.
•
The ground for the shield is at the driver signal source.
Continued on next page
MODBUS TRANSMITTER
15 BST RS485
–
HEADER TEMP SENSOR
13 BST RS485+
3 Shield
I/O BOARD STRIP J3