![background image](http://html1.mh-extra.com/html/watts/aerco-benchmark-omm-0136/aerco-benchmark-omm-0136_operation-and-service-manual_4051813134.webp)
Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 9
– AERTRIM OPERATION
OMM-
0137_E • GF-211 • 12/13/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
134
of
153
BMK3000 AERtrim Values
MENU ITEM
Minimum
Maximum
Default
Settle Time
0
120 Sec
20 Sec
Trim Gain
0.1
5.0
0.250
Max Tries
0
100
15
O
2
Target
(must be
between
O
2
Upper &
O
2
Lower)
14%
3%
8%
6.5%
30%
3%
8%
7.3%
40%
3%
8%
7.5%
50%
3%
8%
7.0%
70%
3%
8%
5.5%
100%
3%
8%
5.0%
O
2
Lower
(must be at
least 1%
lower than
O
2
Upper)
14%
2.5%
5.5%
5.5%
30%
2.5%
5.5%
5.5%
40%
2.5%
5.5%
5.5%
50%
2.5%
5.5%
5.5%
70%
2.5%
5.5%
5.0%
100%
2.5%
5.5%
4.5%
O
2
Upper
(must be at
least 1%
higher than
O
2
Lower)
14%
5.5%
8.5%
7.0%
30%
5.5%
8.5%
7.8%
40%
5.5%
8.5%
8.0%
50%
5.5%
8.5%
7.5%
70%
5.5%
8.5%
6.0%
100%
5.5%
8.5%
5.5%
O
2
Offset
-3.0
3.0
1.0
BMK3000 AERtrim Adjustment Range
CALIBRATION POINT
BLOWER VOLTAGE
Minimum
Maximum
Default
14%
2.60
4.90
2.80
30%
3.60
7.00
4.60
40%
4.60
8.00
5.00
50%
5.00
9.20
5.50
70%
6.10
10.00
6.90
100%
7.60
10.00
9.10