background image

2

Table 1. 

Drain Size for Typical Flow Rates per Valve Size

VALVE SIZE

TYPICAL FLOW RATE 

DRAIN SIZE

2

1

2

"

55 gpm

2"

3"

112 gpm

3"

4"

170 gpm

4"

6", 8", 10"

350 gpm

5"

Figure 2. 

Series 909/LF909-FS Relief Valve Discharge Rates

ZONE PRESSURE (PSIG)

FLOW RATE (GPM)

2

1

2

" – 3"

4" – 10" 

175

150

125

100

75

50

25

0

0  100 200 300 400 500 600 700 800 900

Relief Valve

First 

Check

Second

Check

Second 

Shutoff 

Valve

Inlet 

Shutoff  

Valve

Figure 1. 

Watts Series 909/LF909-FS

Sizes 
2

1

2

" – 10"

Series 909/LF909-FS 

Sizes: 2

1

2

" – 10"

•  The relief valve module on 2

1

2

" – 10" Series 909/LF909-FS assemblies 

may be turned to discharge to the opposite side. To do so, unbolt 

the relief valve and turn the relief valve discharge port to the oppo-

site side. Mount the high pressure hose on the op po site side. This 

should be done by a licensed journeyman, who is rec og nized by 

the authority having jurisdiction, and only when space is critical for 

testing or repair. 

•  

ASSEMBLY:

 If the backflow preventer is disassembled during 

installation, it MUST be reassembled in its proper order. The gate 

valve with the test cock is to be mounted on the inlet side of the 

backflow preventer. The test cock must be on the inlet side of the 

wedge. Failure to reassemble correctly can result in water damage 

due to excessive discharge from the relief port/vent and possible 

malfunction of the backflow preventer.

NOTICE

The flange gasket bolts for the gate valves can loosen in storage 

and shipment. Retighten the bolts during installation to align  

the valves.

High Capacity Relief Series

•  Backflow preventers must be installed in high-visibility locations to 

allow for immediate notice of telltale discharge or other malfunction. 

This location should also facilitate testing and ser vic ing, and protect 

against freezing and vandalism.

•  Installing a backflow preventer in a pit or vault is not rec om mend-

ed. However, if this becomes necessary, Watts highly rec om mends 

that a licensed journeyman, who is recognized by the authority 

having jurisdiction, be consulted. This type of installation and other 

installation procedures must comply with all state and local codes 

and meet the required safety provisions. An air gap below the relief 

port must be maintained so as to avoid flooding and submersion of the 

assembly, which may lead to a cross connection. Figure 1 shows the 

primary components of the Series 909/LF909-FS.

•  Pipelines should be thoroughly flushed to remove foreign material 

before installing the unit. A strainer should be installed ahead of the 

backflow preventer to prevent the disc from unnecessary fouling. Install 

the valve in line with the arrow on the valve body, pointing in the direc-

tion of flow.

 

CAUTION

!

Do not install a strainer ahead of the backflow preventer on seldom-

used, emergency water lines such as fire sprinkler lines. The strainer 

mesh could potentially become clogged with debris present in the 

water and cause water blockage during an emer gen cy.
•  Normal discharge and nuisance spitting are accommodated by the use 

of a Watts air gap fitting and a fabricated indirect waste line. Floor 

drains of the same size MUST be provided in case of excessive dis-

charge. See the relief valve discharge rates in Figure 2 and the typical 

flow rates per valve and drain sizes in Table 1.

•  When a Series 909/LF909-FS backflow preventer is installed for 

dead-end service applications (such as boiler feed lines, cooling 

tower makeup, or other equip ment with periodic flow requirements), 

discharge from the relief vent may occur due to water supply pres-

sure fluctuation during static no-flow con di tions. A check valve may 

be required ahead of the backflow preventer. Before installation, 

see “Troubleshooting,” page 8.

Considerations for Installation

•  

START UP: 

At initial installation and after servicing, the down-

stream shutoff should be closed. Slowly open upstream shutoff 

and allow the backflow preventer to fill slowly. Bleed air at each 

test cock. When the backflow preventer is filled, slowly open the 

down stream shutoff and fill the water supply system. This is  

necessary to avoid dislodging O-rings or causing damage to  

internal  com po nents.

•  

TEST:

 The Series 909/LF909-FS backflow preventer may be test-

ed by a certified tester at the time of installation to ascertain that 

the assembly is in full working order and may be relied upon to 

protect the safe drinking water as per applicable standard.

Flood Sensor

Summary of Contents for 909 Series

Page 1: ...on WARNING WARNING The installation and maintenance of backflow assemblies should be performed by a qualified licensed technician Failure to do so may result in a malfunctioning assembly Local building or plumbing codes may require modifications to the information provided You are required to consult the local building and plumbing codes prior to installa tion If the information provided here is n...

Page 2: ... and local codes and meet the required safety provisions An air gap below the relief port must be maintained so as to avoid flooding and submersion of the assembly which may lead to a cross connection Figure 1 shows the primary components of the Series 909 LF909 FS Pipelines should be thoroughly flushed to remove foreign material before installing the unit A strainer should be installed ahead of t...

Page 3: ...h Test cock No 2 No 3 and No 4 When valve is filled open the downstream shutoff slowly and fill the water supply system This is necessary to avoid water hammer or shock damage The installation of a Watts air gap with the drain line terminating above a floor drain handles any normal discharge or nuisance spit ting through the relief valve However floor drain size may need to be designed to prevent ...

Page 4: ...all pressure differentials Close high valve A and open test cock No 2 Close test cock No 4 Disconnect vent hose at test cock No 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pres sure differential gauge If there is a decrease in the indicated value check valve No 1 is reported as leaking Test No 4 Purpose To test oper...

Page 5: ...e retainers Sizes 21 2 3 turn the seat by one quarter to remove it One wire is drawn out clockwise the other counterclockwise 4 Lift the seat ring straight up to remove it 5 To replace the disc on sizes 21 2 4 remove the retaining nut For sizes 6 10 remove the Allen head socket screws Reverse this procedure to install the new disc For further details contact your tech ni cal sales representative D...

Page 6: ... assembly 5 Inspect the bottom plug and spring assembly During normal field service there is no need to remove this assembly other than inspection Unscrew the assembly with a large pipe wrench CAUTION The spring is retained on the bottom plug and is highly loaded NO attempt should be made in the field to disassemble the bottom plug and spring piston assembly For replacement a complete bottom plug ...

Page 7: ...m and or electri cally isolate the device with plastic pipe immediately upstream and down stream of the device B 6 Valve improperly reassembled B 6 If the valve is dis as sem bled during installation exercise caution when installing check springs in their proper location C Valve exhibits high pressure drop C 1 Fouled strainer C 1 Clean strainer element or replace C 2 Valve too small for flows enco...

Page 8: ...55 4122 0138 Watts com Part Number Add On Retrofit Kit Description Add on and Retrofit Sensor Connection Kits for BMS 88003050 BMS Sensor Connection Kit for LF909 FS Sizes 2 to 10 Includes a sensor activation module with cable power adapter and ground wire Use this kit to activate the integrated flood sensor and enable flood detection capabilities for the relief valve to work with a third party BM...

Page 9: ...DVERTENCIA La instalación y el mantenimiento de los ensambles de reflujo deben ser realizados por un técnico calificado y autorizado El no hacerlo puede resultar en un ensamble defectuoso Las reglamentos locales de construcción o plomería pueden requerir modificaciones a la información proporcionada Debe consultar los reglamentos locales de construcción y plomería antes de realizar la instalación ...

Page 10: ...ientos de instalación deben cumplir con todos los códigos estatales y locales y cumplir con las disposiciones de seguridad requeridas Debe mantenerse un espacio de aire debajo del puerto de alivio para evitar inundaciones e inmersiones del ensamble lo que puede provocar una conexión cruzada La Figura 1 muestra los componentes principales de la serie 909 LF909 FS Las tuberías deben lavarse a fondo ...

Page 11: ...es necesario para evitar golpes de ariete o daños por golpes La instalación de un accesorio de espacio de aire Watts con la línea de drenaje terminando sobre un desagüe en el piso maneja cualquier descarga normal o escupida molesta a través de la válvula de alivio Sin embargo es posible que sea necesario diseñar el tamaño del desagüe del suelo para evitar daños por agua causados por una condición ...

Page 12: ...e la válvula alta A y abra la válvula de prueba N º 2 Cierre la válvula de prueba N º 4 Desconecte la manguera de aireación en la válvula de prueba N º 4 Abra las válvulas B y C purgando al ambiente A continuación el cierre de la válvula B restaura el sistema a una condición estática normal Observe el manómetro diferencial de presión Si hay una disminución en el valor indicado la válvula de retenc...

Page 13: ... Un alambre se extrae en el sentido de las agujas del reloj el otro en sentido antihorario 4 Levante el anillo del asiento hacia arriba para retirarlo 5 Para reemplazar el disco en tamaños de 21 2 in a 4 in 6 35 cm a 10 16 cm retire la tuerca de retención Para tamaños de 6 in a 10 in 15 24 cm a 25 4 cm retire los tornillos Allen Siga este procedimiento en orden inverso para instalar el nuevo disco...

Page 14: ...sario retirar este ensamble más que para la inspección Desenrosque el ensamble con una llave para tubos grandes PRECAUCIÓN El resorte está retenido en el tapón inferior y está muy cargado NO se debe intentar en el campo desmontar el tapón inferior y el ensamble del pistón del resorte Para el reemplazo debe obtenerse de fábrica un ensamble del tapón inferior completo Para obtener más información pó...

Page 15: ...sistema de tuberías y o aísle eléctricamente el dispositivo con una tubería de plástico inmediatamente aguas arriba y aguas abajo del dispositivo B 6 Válvula reensamblada incorrectamente B 6 Si la válvula se desmonta durante la instalación tenga cuidado al instalar los resortes de retención en su ubicación correcta C La válvula muestra una caída de presión alta C 1 Filtro sucio C 1 Limpie el eleme...

Page 16: ... del sensor con cable adaptador de corriente y cable de tierra Use este kit para activar el sensor de inundación integrado y habilitar las capacidades de detección de inundaciones para que la válvula de alivio funcione con una caja de control BMS de terceros no incluida 88003051 Kit de conexión de retroadaptación del sensor BMS para tamaños LF909 de 2 in a 3 in 6 35 cm a 7 62 cm Incluye un sensor ...

Reviews: