background image

4

For repair kits and parts, refer to Backflow 

Prevention Products Repair Kits & Service Parts 

price list PL-RP-BPD at 

watts.com.

Follow the requirements of each test when performed to ensure 

successful installation, operation, and maintenance of the backflow 

preventer.

Test No.1

Purpose:

 To test check valve No. 2 for tightness against reverse flow.

Requirements:

 Valve must be tight against reverse flow under 

all pressure differentials. Slowly open the ‘high’ valve A and the 

‘vent’ valve C, and keep the ‘low’ valve B closed. Open test No. 

4. Indicated pressure differential is expected to decrease slightly. 

If pressure differential continues to decrease (until the vent opens) 

check valve No. 2 is reported as ‘leaking.’

Test No. 2

Purpose:

 To test shutoff No. 2 for tightness.

Requirements:

 After passing test No. 1, continue to test No. 2 by 

closing test cock No. 2. The indicated pressure differential is expected 

to decrease slightly. If pressure differential continues to decrease 

(approaching ‘zero’), shutoff No. 2 is reported to be ‘leaking.’

Test No. 3

Purpose:

 To test check valve No. 1 for tightness.

Requirements:

 Valve must be tight against reverse flow under all 

pressure differentials. Close ‘high’ valve A and open test cock No. 2. 

Close test cock No. 4. Disconnect vent hose at test cock No. 4. 

Open valves B and C, bleeding to atmosphere. Then closing valve B 

restores the system to a normal static condition. Observe the pres-

sure differential gauge. If there is a decrease in the indicated value, 

check valve No. 1 is reported as ‘leaking.’

Test No. 4

Purpose:

 To test operation of pressure differential relief valve.

Requirements:

 The pressure differential relief valve must operate to 

maintain the ‘zone’ between the two check valves at least 2psi less 

than the supply pressure. Close ‘vent’ valve C. Open ‘high’ valve 

A. Open the ‘low’ valve B very slowly until the differential gauge 

needle starts to drop. Hold the valve at this position and observe the 

gauge reading when the first discharge is noted from the relief valve. 

Record this as the opening differential pressure of the relief valve.

 

NOTICE

The differential gauge needle MUST drop slowly. Close test 

cocks No. 2 and No. 3. Use ‘vent’ hose to relieve pressure from 

the test kit by opening valves A, B, and C. Remove all test 

equipment and open shutoff No. 2.

Testing — Reduced Pressure Zone Assemblies

Figure 4. 

Ball Type Test Valves

(A)

(C)

(B) 

Needle
Valve

High Hose
(Yellow)

Low Hose
(White or Red)

Vent Hose 

(Blue)

Test Cock No. 1

Test Cock No. 2

Test Cock No. 3

Test Cock No. 4

Summary of Contents for 909 Series

Page 1: ...on WARNING WARNING The installation and maintenance of backflow assemblies should be performed by a qualified licensed technician Failure to do so may result in a malfunctioning assembly Local building or plumbing codes may require modifications to the information provided You are required to consult the local building and plumbing codes prior to installa tion If the information provided here is n...

Page 2: ... and local codes and meet the required safety provisions An air gap below the relief port must be maintained so as to avoid flooding and submersion of the assembly which may lead to a cross connection Figure 1 shows the primary components of the Series 909 LF909 FS Pipelines should be thoroughly flushed to remove foreign material before installing the unit A strainer should be installed ahead of t...

Page 3: ...h Test cock No 2 No 3 and No 4 When valve is filled open the downstream shutoff slowly and fill the water supply system This is necessary to avoid water hammer or shock damage The installation of a Watts air gap with the drain line terminating above a floor drain handles any normal discharge or nuisance spit ting through the relief valve However floor drain size may need to be designed to prevent ...

Page 4: ...all pressure differentials Close high valve A and open test cock No 2 Close test cock No 4 Disconnect vent hose at test cock No 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pres sure differential gauge If there is a decrease in the indicated value check valve No 1 is reported as leaking Test No 4 Purpose To test oper...

Page 5: ...e retainers Sizes 21 2 3 turn the seat by one quarter to remove it One wire is drawn out clockwise the other counterclockwise 4 Lift the seat ring straight up to remove it 5 To replace the disc on sizes 21 2 4 remove the retaining nut For sizes 6 10 remove the Allen head socket screws Reverse this procedure to install the new disc For further details contact your tech ni cal sales representative D...

Page 6: ... assembly 5 Inspect the bottom plug and spring assembly During normal field service there is no need to remove this assembly other than inspection Unscrew the assembly with a large pipe wrench CAUTION The spring is retained on the bottom plug and is highly loaded NO attempt should be made in the field to disassemble the bottom plug and spring piston assembly For replacement a complete bottom plug ...

Page 7: ...m and or electri cally isolate the device with plastic pipe immediately upstream and down stream of the device B 6 Valve improperly reassembled B 6 If the valve is dis as sem bled during installation exercise caution when installing check springs in their proper location C Valve exhibits high pressure drop C 1 Fouled strainer C 1 Clean strainer element or replace C 2 Valve too small for flows enco...

Page 8: ...55 4122 0138 Watts com Part Number Add On Retrofit Kit Description Add on and Retrofit Sensor Connection Kits for BMS 88003050 BMS Sensor Connection Kit for LF909 FS Sizes 2 to 10 Includes a sensor activation module with cable power adapter and ground wire Use this kit to activate the integrated flood sensor and enable flood detection capabilities for the relief valve to work with a third party BM...

Page 9: ...DVERTENCIA La instalación y el mantenimiento de los ensambles de reflujo deben ser realizados por un técnico calificado y autorizado El no hacerlo puede resultar en un ensamble defectuoso Las reglamentos locales de construcción o plomería pueden requerir modificaciones a la información proporcionada Debe consultar los reglamentos locales de construcción y plomería antes de realizar la instalación ...

Page 10: ...ientos de instalación deben cumplir con todos los códigos estatales y locales y cumplir con las disposiciones de seguridad requeridas Debe mantenerse un espacio de aire debajo del puerto de alivio para evitar inundaciones e inmersiones del ensamble lo que puede provocar una conexión cruzada La Figura 1 muestra los componentes principales de la serie 909 LF909 FS Las tuberías deben lavarse a fondo ...

Page 11: ...es necesario para evitar golpes de ariete o daños por golpes La instalación de un accesorio de espacio de aire Watts con la línea de drenaje terminando sobre un desagüe en el piso maneja cualquier descarga normal o escupida molesta a través de la válvula de alivio Sin embargo es posible que sea necesario diseñar el tamaño del desagüe del suelo para evitar daños por agua causados por una condición ...

Page 12: ...e la válvula alta A y abra la válvula de prueba N º 2 Cierre la válvula de prueba N º 4 Desconecte la manguera de aireación en la válvula de prueba N º 4 Abra las válvulas B y C purgando al ambiente A continuación el cierre de la válvula B restaura el sistema a una condición estática normal Observe el manómetro diferencial de presión Si hay una disminución en el valor indicado la válvula de retenc...

Page 13: ... Un alambre se extrae en el sentido de las agujas del reloj el otro en sentido antihorario 4 Levante el anillo del asiento hacia arriba para retirarlo 5 Para reemplazar el disco en tamaños de 21 2 in a 4 in 6 35 cm a 10 16 cm retire la tuerca de retención Para tamaños de 6 in a 10 in 15 24 cm a 25 4 cm retire los tornillos Allen Siga este procedimiento en orden inverso para instalar el nuevo disco...

Page 14: ...sario retirar este ensamble más que para la inspección Desenrosque el ensamble con una llave para tubos grandes PRECAUCIÓN El resorte está retenido en el tapón inferior y está muy cargado NO se debe intentar en el campo desmontar el tapón inferior y el ensamble del pistón del resorte Para el reemplazo debe obtenerse de fábrica un ensamble del tapón inferior completo Para obtener más información pó...

Page 15: ...sistema de tuberías y o aísle eléctricamente el dispositivo con una tubería de plástico inmediatamente aguas arriba y aguas abajo del dispositivo B 6 Válvula reensamblada incorrectamente B 6 Si la válvula se desmonta durante la instalación tenga cuidado al instalar los resortes de retención en su ubicación correcta C La válvula muestra una caída de presión alta C 1 Filtro sucio C 1 Limpie el eleme...

Page 16: ... del sensor con cable adaptador de corriente y cable de tierra Use este kit para activar el sensor de inundación integrado y habilitar las capacidades de detección de inundaciones para que la válvula de alivio funcione con una caja de control BMS de terceros no incluida 88003051 Kit de conexión de retroadaptación del sensor BMS para tamaños LF909 de 2 in a 3 in 6 35 cm a 7 62 cm Incluye un sensor ...

Reviews: