Watlow PM LEGACY™ Limit Controller
•
62
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
A.LA
A.LA
Alarm (1 to 4)
Latching
Turn latching on or off.
A latched alarm has
to be turned off by the
user.
nLAt
Non-Latch-
ing (60)
LAt
Latching (49)
Non-
Latch-
ing
Instance 1
Map 1Map 2
1492 1892
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
7
27
9007 uint
RWES
A.bL
A.bL
Alarm (1 to 4)
Blocking
Select when an alarm
will be blocked. After
startup and/or after
the set point chang-
es, the alarm will be
blocked until the pro-
cess value enters the
normal range.
oFF
Off (62)
Str
Startup (88)
StPt
Set Point
(85)
both
Both (13)
Off
Instance 1
Map 1Map 2
1494 1894
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
8
28
9008 uint
RWES
A.Si
A.Si
Alarm (1 to 4)
Silencing
Turn silencing on to al-
low the user to disable
this alarm.
oFF
Off (62)
on
On (63)
Off
Instance 1
Map 1Map 2
1490 1890
Offset to next
instance (Map
1 50,
for Map 2
60)
0x6D
(109)
1 to 4
6
29
9006 uint
RWES
A.dSP
A.dSP
Alarm (1 to 4)
Display
Display an alarm mes-
sage when an alarm is
active.
oFF
Off (62)
on
On (63)
On
Instance 1
Map 1Map 2
1510 1910
Offset to next
instance (Map
1 50,
for Map 2
60)
0x6D
(109)
1 to 4
0x10
(16)
30
9016 uint
RWES
** R: Read, W: Write, E: EEPROM, S: User Set