Watlow PM LEGACY™ Limit Controller
•
47
•
Chapter 5 Operations Page
Operations Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fib-
us
In-
dex
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
A.CLr
A.CLr
Alarm (1 to 4)
Clear Alarm
Write to this reg-
ister to clear an
alarm
CLr
Clear (1003)
ignr
Ignore (204)
- - - -
Instance 1
Map 1Map 2
1504 1904
Offset to
next instance
(Map1 1
50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0x0D (13)
- - - - 9026
uint
W
A.sir
A.Sir
Alarm (1 to 4)
Silence Alarm
Write to this reg-
ister to silence an
alarm
siL
Silence (1010)
Instance 1
Map 1Map 2
1506 1906
Offset to
next instance
(Map1 1
50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0x0E (14)
- - - - 9027
uint
W
A.st
A.St
Alarm (1 to 4)
State
Current state of
alarm
Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)
- - - -
Instance 1
Map 1Map 2
1496 1896
Offset to
next instance
(Map1 1
50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
9
- - - - 9009
uint
R
No Dis-
play
Alarm (1 to 4)
Alarm Clearable
Indicates if alarm
can be cleared.
No (59)
Yes (106)
Instance 1
Map 1Map 2
1502 1902
Offset to
next instance
(Map1 1
50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xC (12)
- - - - 9012
uint
R
No Dis-
play
Alarm (1 to 4)
Alarm Silenced
Indicates if alarm is
silenced.
No (59)
Yes (106)
- - - -
Instance 1
Map 1Map 2
1500 1900
Offset to
next instance
(Map1 1
50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0x0B (11)
- - - - 9011
uint
R
** R: Read, W: Write, E: EEPROM, S: User Set