Watlow PM LEGACY™ Limit Controller
•
57
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
LL.s
LL.S
Limit
Low Limit Set Point
Set the low process
value that will trigger
the limit.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1 Map 2
684
724
0x70
(112)
1
3
38
12003 float
RWES
sfn.a
SFn.A
Limit
Source Function A
Set the source for the
limit reset function.
nonE
None (61)
dio
Digital I/O
(1142)
fUn
Function Key
(1001)
None
Instance 1
Map 1 Map 2
- - - -
748
0x70
(112)
1
0x0F
(15)
- - - -
12015 uint
RWES
si.a
Si.A
Limit
Source Instance A
Set the instance of
the function selected
above.
1 to 12
1
- - - -
0x70
(112)
1
0x10
(16)
- - - - 12016 uint
RWES
L.Cr
LCr
Limit
Clear Limit
Clear limit once limit
condition is safe.
CLr
Clear (129)
ignr
Ignore (204)
- - - -
Instance 1
Map 1 Map 2
680
720
0x70
(112)
1
1
- - - - 12014 uint
W
L.st
L.St
Limit
Limit Status
Reflects whether or
not the limit is in a
safe or failed mode.
faiL
Fail (32)
safE
Safe (1667)
- - - -
Instance 1
Map 1 Map 2
- - - -
744
0x70
(112)
1
0x0D
(13)
- - - - 12013 uint
R
No Dis-
play
Limit
Limit State
Clear limit once limit
condition is cleared.
Off (62)
None (61)
Limit High (51)
Limit Low (52)
Error (28)
- - - -
Instance 1
Map 1 Map 2
690
730
0x70
(112)
1
6
- - - - 12006 uint
R
** R: Read, W: Write, E: EEPROM, S: User Set