F4T Base Specifications
Line Voltage/Power (Minimum/Maximum Ratings)
• High voltage option: 85 to 264V~
(ac) 47/63Hz
• Low voltage option: 20.4 to 30.8V (
~ ac) (
Î
dc), 47/63Hz
• Power consumption: 23 W, 54VA maximum
• Data retention upon power failure via non-volatile memory
Environment
•
NEMA 4X/IP65 - front panel mount configuration only
•
0 to 122°F (-18 to 50°C) operating temperature
•
-40 to 185°F (-40 to 85°C) storage temperature
• 0 to 90% RH, non-condensing
Accuracy
•
Calibration accuracy and sensor conformity: ±0.1% of span, ±1°C @ the calibrated ambi
-
ent temperature and rated line voltage
• Types R, S, B; 0.2%
•
Type T below -50°C; 0.2%
•
Calibration ambient temperature @ 77 ±5°F (25°C
±
3°C)
•
Accuracy span :1000 °F (540°C) min.
•
Temperature stability: ±0.1 °F/°F (±0.1°C/°C) rise in ambient maximum
Agency Approvals
• UL
®
Listed to UL 61010 File E185611 QUYX
•
CSA 22.2#14, File 158031
•
FM Class 3545 (configurations with limit modules)
•
RoHS by design, China RoHS Level , W.E.E.E.
•
CE
• Windows
®
Hardware Certification
Controller
• 1 to 4 PID or ON-OFF control loops or 1 to 2 control loops with 1 to 2 cascade loops
• User selectable action: heat, cool or heat/cool
•
Auto-tune with TRU-TUNE
®
+ adaptive control algorithm
•
Control sampling rates: input = 10Hz, outputs = 10Hz
• 1 to 6 Limit loops
6