Watlow F4T Install & Troubleshooting
•
44
•
Chapter 8 Appendix
Number of Function Blocks by Ordering Option
Function Block
Basic
Set 1
Set 2
Alarm
6
8
14
Compare
None
4
16
Counter
None
4
16
Linearization
4
4
8
Logic
None
12
24
Math
None
12
24
Process Value
4
4
8
Special Output
Function
None
2
4
Timer
None
6
16
Variable
4
12
24
•
Compare 16 total
Off, greater than, less than, equal, not equal, greater than or equal, less than or equal
•
Counter 16 total
Counts up or down loads, predetermined value on load signal. Output is active when
count value equals predetermined target value
•
Logic 24 total
Off, and, nand, or, nor, equal, not equal, Latch
•
Linearization 8 total
Interpolated or stepped relationship
•
Math 24 total
Off, average, process scale, deviation scale, differential (subtraction), ratio (divide),
add, multiply, absolute difference, min., max., square root, sample and hold
•
Process Value 8 total
Off, sensor backup, average, crossover, wet/dry bulb, switch over, differential (subtrac-
tion), ratio (divide), add, multiply, absolute difference, min., max., square root
•
Special Output Function 4 total
- Compressor
turns on-off compressor for one or two loops (cool and dehumidify with
single compressor)
- Motorized Valve
turns on-off motor open/closed outputs to cause valve to represent
desired power level
-
Sequencer
turns on-off up to four outputs to distribute a single power across all outputs
with linear and progressive load wearing
•
Timer 16 total
-
On Pulse
produces output of fixed time on active edge of timer run signal
-
Delay
output is a delayed start of timer run, off at same time
-
One Shot
oven timer
-
Retentive
measures timer run signal, output on when accumulated time exceeds target
•
Variable 24 total
User value for digital or analog variable