Chapter 5: LogicPro and Modbus Reference
PPC-2000 User’s Guide
182
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
Setpoint Source
This parameter determines how the setpoint for the channel is
set. Select
User
for normal closed-loop control applications.
Select a channel output (
Channel # Out
) for cascade control.
Select an analog input for ratio control, differential control,
remote setpoint, or process variable retransmit. A value of 0
indicates a user set setpoint. See
through
for values to select a channel
output or analog input as the source of the setpoint value.
Setpoint Ratio
For ratio control, differential control, and remote setpoint
applications, set the ratio by which the analog input value
selected as the
Setpoint Source
is multiplied to calculate the
.) This
parameter may be set to any value from -30000 to 30000
corresponding to a range of -300.00 to 300.00.
Setpoint Offset
For ratio control, differential control, and remote setpoint
applications set the offset which is added to the product of the
analog input value selected as the
Setpoint Source
and the
Setpoint Ratio
to calculate the setpoint. (
109,Differential Control on page 112,
and
This parameter may be set to any value from -32768 to 32767
The number of decimal places depends on the
Input Type
Maximum Setpoint
This parameter determines the maximum value the PPC will
accept for the setpoint of the channel. This parameter is also
used to scale a cascade channel. (See
The range is the same as that of the input type for the
channel.
Minimum Setpoint
This parameter determines the minimum value the PPC will
accept for the setpoint of the channel. This parameter is also
used to scale a cascade channel.
(
See
The range is the same as that of the input type for the
channel.
Heat/Cool Output Type
This parameter specifies the type of output signal and
determines whether the PID or on/off control algorithm is used
for the channel. See
information on control terminology and definitions, refer to
Chapter 6, Control Terminology
.
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...